INSTALLATION
Horizontal Venting with Two (2) 90o Elbows
INSTALLATION |
|
|
| One 90o elbow = Two 45o elbows. | |||
| Option |
| V | H + H1 | With | these options, | |
|
| A) | 2' | Min. | 2' Max. | maximum total pipe length | |
|
| B) | 3' | Min. | 5' Max. | is 30 feet with minimum | |
|
| C) | 4' | Min. | 6' Max. | of 6 | feet total vertical |
|
| and maximum 8 feet total | |||||
|
| D) | 5' | Min. | 7' Max. | ||
|
| horizontal. | |||||
|
| E) | 6' Min. | 8' Max. |
|
| |
|
| VENT RESTRICTOR SETTING: |
|
| |||
| H1 | When total vertical exceeds total horizontal by 2x the vent | |||||
| restrictor setting is set to 1. |
|
| ||||
|
|
|
| ||||
|
| V |
|
|
|
|
|
|
| Please note minimum 1 foot between 90o elbows is | |||||
|
| required. |
|
|
|
|
|
Horizontal Venting with Three (3) 90o Elbows
One 90o elbow = Two 45o elbows.
Option V | H | V + V1 H + H1 |
A)0' Min. 1' Max. 1' Min. 1' Max.
B)1' Min. 2' Max. 3' Min. 3' Max.
C)2' Min. 2' Max. 5' Min. 4' Max.
D)3' Min. 2' Max. 7' Min. 5' Max.
E)4' Min. 3 Max. 9' Min. 6' Max.
F)5' Min. 4' Max. 10' Min. 7' Max.
G)6' Min. 5' Max. 11' Min. 8' Max.
H)7' Min. 6' Max. 12' Min. 9' Max.
With these options, max. total pipe length is 30 feet with min. of 12 feet total vertical and max. 9 feet total horizontal.
Please note min. 1 foot between 90o elbows is required.
VENT RESTRICTOR SETTING:
When total vertical exceeds total horizontal by 3x the vent restrictor setting is set to 1.
18 | Regency® P40 Direct Vent Gas Fireplace |