INSTALLATION
P36-NG System Data
For 0 to 4500 feet altitude
Burner Inlet Orifice Sizes: #37( 2.65mm)
Max. Input Rating | 33 mj |
Min. Input Rating | 20 mj |
|
|
Supply Pressure | min.1.25 kPa |
Manifold Pressure |
|
(High) | 0.9 kPa |
Electrical: 240 V A.C. System.
Circulation Fan: variable speed 130 CFM.
Log Set: Ceramic fi bre, 7 per set.
Flue System: Simpson
Flue System or Regency® Direct
Flue System (Flex)
P36-LPG System Data
For 0 to 2000 feet altitude
Burner Inlet Orifice Sizes: #52 (1.6 mm)
Max. Input Rating | 31 mj |
Min. Input Rating | 18 mj |
| |
For 0 to 4500 feet Altitude: | |
Supply Pressure | min 2.75 kPa |
Manifold Pressure |
|
GAS LINE
INSTALLATION
The gas line can be brought through either the right or the left side of the appliance. The gas valve is situated on the right hand side of the unit and the gas inlet is on the right hand side of the valve.
Note: If the gas line is being installed from the left side, be sure to leave room to accommodate servicing of the fan.
The gas line connection may be made of rigid pipe, copper pipe or an approved fl ex connector. (If you are using rigid pipe, ensure that the valve can be removed for servicing.) Since some municipalities have additional local codes it is always best to consult with your local authorities and the
When using copper or fl ex connectors use only approved fi ttings. Always provide a union so that gas lines can be easily disconnected for servicing. Flare nuts for copper lines and fl ex connectors are usually considered to meet this requirement.
Important:Always check for gas leaks with a soap and water solution or gas leak detector. Do not use open flame for leak testing.
PILOT ADJUSTMENT
Periodically check the pilot flames. Correct flame pattern has three strong blue flames: 1 flowing around the thermopile, 1 around the thermocouple and 1 flowing across the burner (it does not have to be touching the burner).
Note: Ifyouhaveanincorrectflamepattern, contact your Regency® dealer for further instructions.
Incorrect flame pattern will have small, probably yellow flames, not coming into proper contact with the rear burner or thermopile or thermocouple.
(High) | 2.7 kPa |
Electrical: 240 V A.C. System.
Circulation Fan: variable speed 130 CFM.
Log Set: Ceramic fi bre, 7 per set.
Flue System: Simpson
AERATION
ADJUSTMENT
The air shutter can be adjusted by moving the adjusting wire up or down. The wire is accessed through the bottom louvre opening. Open the air shutter for a blue fl ame or close for a yellower
flame. The burner aeration is factory set but may need adjusting due to either the local gas supply or altitude. This adjustment is performed by the gas fi tter.
Minimum Air Shutter Opening:
8 mm | NG |
Full Open | LPG |
CAUTION: Carbon will be produced if air shutter is closed too much.
Note: Any damage due to carboning resulting from improperly setting the aeration controls is NOT covered under warranty.
Closed - Tall yellow
Open - Short Blue
GAS PIPE PRESSURE
TESTING
The appliance must be isolated from the gas supply piping system by closing its individual manual
The manifold pressure is controlled by a regulator built into the gas control, and should be checked at the pressure test point.
Note: To properly check gas pressure, both inlet and manifold pressures should be checked using the valve pressure ports on the valve.
1)Make sure the valve is in the "OFF" position.
2)Loosen the "IN" and/or "OUT" pressure tap(s), turning counterclockwise with a 1/8" wide fl at screwdriver.
3)Attach manometer to "IN" and/or "OUT" pressure tap(s) using a 5/16" ID hose.
20 | Regency® |