INSTALLATION
FLUEING
Regency® Direct Vent System (Flex)
Horizontal Terminations Only
These fl ueing systems, in combination with the P36 Room Sealed Gas Fireplace, have been tested and listed as a Direct Vent type fl ue system by the Australian Gas Association. The location of the termination cap must conform to the requirements in the Flue Terminal Locations diagram in section "Exterior Flue Termination Locations."
Regency® Direct Vent (Flex) System Termination Kit (Part #
1)175mm dia. fl exible liner (1200mm length)
2)100mm dia. fl exible liner (1200mm length)
3)spring spacers (4)
4)thimble (2)
5)AstroCap termination cap (1)
6)screws (12)
7)tube of Mill Pac (1)
8)plated screws (8)
9)screws #8 x
If longer runs are needed, the Regency® Direct Vent system (Flex) #
1)175mm dia. fl exible liner (3.0m length)
2)100mm dia. fl exible liner (3.0m length)
3)spring spacers (7)
4)thimble (2)
5)AstroCap termination cap (1)
6)screws (12)
7)tube of Mill Pac (1)
8)plated screws (8)
9)screws #8 x
| Wall Thimble |
| AstroCap |
4" (102mm) | Termination Cap |
dia. flue pipe | (Part# |
| (patented) | |
spring spacer | ||
(173mm) | ||
| ||
dia. Flue pipe |
|
Notes:
1)Liner sections should be continuous without any joints or seams.
2)Only Flex pipe purchased from Regency® may be used for Flex installations.
3)If you are installing the P36 into a Regency® Mantel Kit, use the minimum horizontal vent height
Regency® | 11 |