Sanyo CH1852, CH0952 Other Component Specifications, Indoor Unit, KHS0951, KHS1251, KHS1852

Models: KHS1852-S CH0952 CH1852

1 98
Download 98 pages 12.98 Kb
Page 15
Image 15
2-3. Other Component Specifications

2-3. Other Component Specifications

2-3-1. Indoor Unit

(1) Indoor unit

KHS0951

 

 

 

 

Transformer

 

ATR-T4

 

 

 

Rating

Primary

AC 115V, 60Hz

 

Secondary

19V, 0.5A

 

 

 

 

Thermistor (Coil sensor)

DTN-TKS131B

 

 

 

Resistance

kΩ

32°F (0°C) 15 ± 2%

 

 

 

 

Thermistor (Room sensor in lamp Ass’y)

DTN-TKS134B

 

 

 

Resistance

kΩ

77°F (25°C) 5 ± 3%

 

 

 

 

 

DATA SUBJECT TO CHANGE WITHOUT NOTICE.

(2) Indoor unit

KHS1251

 

 

 

 

Transformer

 

ATR-T4

 

 

 

Rating

Primary

AC 115V, 60Hz

 

Secondary

19V, 0.5A

 

 

 

 

 

Thermistor (Coil sensor)

DTN-TKS131B

 

 

 

Resistance

kΩ

32°F (0°C) 15 ± 2%

 

 

 

 

Thermistor (Room sensor in lamp Ass’y)

DTN-TKS134B

 

 

 

Resistance

kΩ

77°F (25°C) 5 ± 3%

 

 

 

 

 

DATA SUBJECT TO CHANGE WITHOUT NOTICE.

(3) Indoor unit

KHS1852

 

 

 

 

Transformer

 

ATR-T5

 

 

 

Rating

Primary

AC 230V, 60Hz

 

Secondary

19V, 0.5A

 

 

 

 

 

Thermistor (Coil sensor)

DTN-TKS131B

 

 

 

Resistance

kΩ

32°F (0°C) 15 ± 2%

 

 

 

 

Thermistor (Room sensor)

DTN-TKS142B

 

 

 

Resistance

kΩ

77°F (25°C) 5 ± 3%

 

 

 

DATA SUBJECT TO CHANGE WITHOUT NOTICE.

11

Page 15
Image 15
Sanyo CH1852, CH0952, KHS1852-S service manual Other Component Specifications, Indoor Unit, KHS0951, KHS1251