7. INSTALLATION INSTRUCTIONS

7. INSTALLATION INSTRUCTIONS

7-1. Installation Site Selection

7-1-1. Indoor Unit

Indoor unit

WARNING

AVOID:

direct sunlight.

To prevent abnormal heat generation and the possibility of fire, do not place obsta- cles, enclosures and grilles in front of or surrounding the air conditioner in a way that may block air flow.

7-1. Installation Site Selection Drain hose

Outside drainage

Fig. 1

nearby heat sources that may affect performance of the unit.

areas where leakage of flammable gas may be expected.

places where large amounts of oil mist exist.

DO:

select an appropriate position from which every cor-

2" (5 cm) min. *6" (15 cm) min.

*KHS1852 only

2" (5 cm) min.

 

*6" (15 cm) min.

2" (5 cm) min.

 

*6" (15 cm) min.

Front View

Fig. 2

ner of the room can be uniformly cooled. (High on a

wall is best.)

select a location that will hold the weight of the unit.

select a location where tubing and drain hose have

the shortest run to the outside. (Fig. 1)

allow room for operation and maintenance as well as

unrestricted air flow around the unit. (Fig. 2)

install the unit within the maximum elevation differ-

INDOOR

Tubing length (L)

UNIT

 

Elevation

OUTDOOR

difference (H)

UNIT

 

Fig. 3a

ence (H) above the outdoor unit and within a total

tubing length (L) from the outdoor unit as detailed in

Table 1 and Fig. 3a.

Table 1

CAUTION

For stable operation of the air conditioner, do not install wall-mounted type indoor units under 5 ft. (1.5 m) from floor level.

Fig. 3b

Indoor unit

Wall

Minimum height from floor level 5 ft. (1.5 m)

Floor level

Max. Allowable Tubing

Limit of Tubing

Limit of Elevation

Required Amount of

 

Length at Shipment

Length (L)

Difference (H)

Additional Refrigerant

Model

(ft.)

(ft.)

(ft.)

(oz./ft.)*

 

25

50

23

a) 0.16

9,000 BTU

 

 

 

 

 

25

65

23

b) 0.27

12,000/18,000 BTU

 

 

 

 

 

*If total tubing length becomes a) 25 to 50 ft. (max.), b) 25 to 65 ft. (max.) charge additional refrigerant (R22) by a) 0.16 oz./ft., b) 0.27 oz./ft. No additional compressor oil is necessary.