9-2-3. Only outdoor unit does not run.

9-2-3. Only outdoor unit does not run.

A. Check setting temperature.

COOL

Is room temperature too low ?

NO

Try to lower setting temperature by temperature setting button (A. Check setting temperature. button).

Outdoor unit still does not run.

Try to run using another remote control unit.

OK

Remote control unit is defective.

B. Check PCB Ass'y in either indoor or outdoor unit.

• Check voltage between terminals

OK

No. 3(+) and No. 4 at terminal plate.

 

(DC 24V)

 

HEAT

Is room temperature too high ?

NO

Try to raise setting temperature by temperature setting button ( 9-2-4. Only indoor unit does not run. button).

Outdoor unit still does not run.

Try to run using another remote control unit.

OK

Remote control unit is defective.

• Outdoor PCB Ass'y is defective.

No voltage appears.

• Indoor PCB Ass'y is defective.

9-2-4. Only indoor unit does not run.

• Indoor PCB Ass'y is defective.