9-2. Air conditioner does not operate.
9-2-1. Circuit breaker trips (or fuse blows).
A. When the circuit breaker is set to ON, it is tripped soon. (Resetting is not possible.)
●There is a possibility of ground fault.
●Check insulation resistance.
If resistance value is 2M½ or less, insulation is defective (“NO”).
Indoor
unit
1
2
3
4
5
6
G
21
Outdoor
unit
18
27
G G
1
Power supply wiring
L2
L1
Ground
Circuit breaker
Power supply
WARNING
*Set circuit breaker to OFF.
1Remove both power supply wires and
•Measure insulation resistance of outdoor unit.
2Remove
•Measure insulation resistance of indoor unit.
NO
NO
Insulation of outdoor unit is defective.
•Measure insulation resistance of electrical parts in outdoor unit.
Insulation of indoor unit is defective.
•Measure insulation resistance of electrical parts in indoor unit.
55