3. Implementation of the communication option cards

3. 2. 2. Reminder of the various connection methods:

ATV 61 RJ45 connector on TSXSCA50 or other screw terminals: Use cable VW3 A8 306 D30 (RJ45 to stripped end, 3 meters)

8........................1

2 = 0 V - brown

3 = D_B - blue

5 = D_A - white/blue

t

1

0VL

2

0VL

3

D(A)

4

D(B)

5

2 = 0 V

4= D_A

5= D_B

ATV 61 RJ45 connector on TSXSCA62: Use cable VW3 A8 306 (RJ45 to 15-way Sub-D)

8........................1

2 = 0 V - brown

3 = D_B - blue

5 = D_A - white/blue

1 2 3 4 5 6 7 8

9 10 11 12 13 14 15

15 = 0 V

14= D_A 7 = D_B

3. 2. 2. 1. Configuring the drive

There are two possible scenarios.

Scenario 1 Using the built-in port when replacing the VW3A58303 Modbus/Unitelway option card

As the PowerSuite software workshop is not able to anticipate this scenario, the communication, address and protocol-format parameters must be entered manually:

Configuring the address

Transfer the Altivar 38 parameters to the Altivar 61 using the integrated display terminal, the graphic display terminal or the PowerSuite software workshop:

The configuration of the Modbus network parameters can be accessed via the [MODBUS NETWORK] (Md￿I-) submenu in the [1.9 - COMMUNICATION] (COM￿-) menu.

Modbus parameter

Description/Possible values

Terminal display

Default value

 

 

 

 

[Modbus Address] (Add)

1 to 247

[1] (1) to [247] (247)

[Off] (OFF)

 

Drive Modbus disabled (0)

 

 

 

 

 

 

[Modbus baud rate] (tbr)

4800 bps

[4.8 Kbps] (4￿8)

[19200] (19￿2)

 

9600 bps

[9.6 Kbps] (9￿6)

 

 

19200 bps

[19.2 Kbps] (19￿2)

 

 

38400 bps

[38.4 Kbps] (38￿4)

 

 

 

 

 

[Modbus format] (tFO)

8 data bits, odd parity, 1 stop bit

[8-0-1] (8o1)

[8 E 1] (8E1)

 

8 data bits, even parity, 1 stop bit

[8-E-1] (8E1)

 

 

8 data bits, no parity, 1 stop bit

[8-N-1] (8n1)

 

 

8 data bits, no parity, 2 stop bits

[8-N-2] (8n2)

 

Configuring the drive control mode

Check and configure the control mode applied to the drive in the [1.6 - COMMAND] (CtL-)menu on the graphic display terminal, the integrated display terminal or the PowerSuite software workshop.

[Profile] (CHCF) = [8 serie] (SE8)

40