3. Implementation of the communication option cards

Option card fault

The [internal com. link] (ILF-)fault appears when the following serious problems occur:

-Hardware fault on the option card

-Dialog fault between the option card and the drive

The [Internal link fault 1] (ILF1) diagnostic parameter can be used to obtain more detailed information about the origin of the last [internal com. link] (ILF) fault:

This parameter can be accessed on the graphic display terminal only, in the [1.10 DIAGNOSTICS] (DGt-)menu, [MORE FAULT INFO] (AFI-).

Value

Description of parameter values

0

No fault

 

 

1

Loss of internal communication with the drive

 

 

2

Hardware fault detected

 

 

3

Error in the EEPROM checksum

 

 

4

Faulty EEPROM

 

 

5

Faulty Flash memory

 

 

6

Faulty RAM memory

 

 

7

Faulty NVRAM memory

 

 

Value

Description of parameter values

8

Faulty analog input

 

 

9

Faulty analog output

 

 

10

Faulty logic input

 

 

11

Faulty logic output

 

 

101

Unknown card

 

 

102

Exchange problem on the drive internal bus

 

 

103

Time out on the drive internal bus (500 ms)

 

 

When the External Fault function is used via a communication card, the Altivar 38 would display EPF, but the Altivar 61 now displays EPF2.

When the Fast Stop function is used via a communication card, the Altivar 38 would display RDY, but the Altivar 61 now displays FST.

It is essential to follow the Altivar 38 internal variables manual when the Altivar 61 is being used in 8 serie mode. If not, migration may not proceed smoothly.