3. Implementation of the communication option cards

3. 3. Communication via Unitelway/Modbus network and VW3 A3 303 option card

3. 3. 1. Reminder of possible connection methods

ATV38

 

 

ATV 61

3

= D(A)

3

= D(A)

4

= 0 V

4

= 0 V

7

= D(B)

7

= D(B)

If the chosen communication interface is the VW3 A3 303 option card (Modbus RTU/Jbus/Ascii, Unitelway) both the address and the protocol format must be configured manually.

3. 3. 2. Configuring the drive address on the Modbus/Unitelway network

Transfer the Altivar 38 address to the Altivar 61:

An Altivar 38 was identified on the bus by its address, coded between 0 and 31.

The address corresponds to the number represented by the binary value 1 or 0 of the 8 card switches (in fact only micro-switches 3 to 7 are used).

The least significant bits are on the right.

Transfer the Altivar 38 address to the Altivar 61 using the 8 switches on the right of the card; the value 0 being the OFF position, the value 1 the ON position.

The least significant bits are on the right.

On the Altivar 38, the binary value 1 of a switch is in the up position, on the Altivar 61 this position is reversed, and the value 1 is effective in the down position.

Example

ATV38

 

ATV 61

Address 11 = 2#0001011

 

Address 11 = 2#0001011

Address

ATV38 switches

 

ATV61 switches

 

12345678

 

12345678

0

0000 0000

 

0000 0000

 

 

 

 

1

0000 0010

 

0000 0001

 

 

 

 

2

0000 0100

 

0000 0010

 

 

 

 

3

0000 0110

 

0000 0011

 

 

 

 

4

0000 1000

 

0000 0100

 

 

 

 

5

0000 1010

 

0000 0101

 

 

 

 

6

0000 1100

 

0000 0110

 

 

 

 

7

0000 1110

 

0000 0111

 

 

 

 

8

0001 0000

 

0000 1000

 

 

 

 

9

0001 0010

 

0000 1001

 

 

 

 

10

0001 0100

 

0000 1010

 

 

 

 

11

0001 0110

 

0000 1011

 

 

 

 

12

0001 1000

 

0000 1100

 

 

 

 

13

0001 1010

 

0000 1101

 

 

 

 

14

0001 1100

 

0000 1110

 

 

 

 

15

0001 1110

 

0000 1111

 

 

 

 

Address

ATV38 switches

 

ATV61 switches

 

12345678

 

12345678

16

0010 0000

 

0001 0000

 

 

 

 

17

0010 0010

 

0001 0001

 

 

 

 

18

0010 0100

 

0001 0010

 

 

 

 

19

0010 0110

 

0001 0011

 

 

 

 

20

0010 1000

 

0001 0100

 

 

 

 

21

0010 1010

 

0001 0101

 

 

 

 

22

0010 1100

 

0001 0110

 

 

 

 

23

0010 1110

 

0001 0111

 

 

 

 

24

0011 0000

 

0001 1000

 

 

 

 

25

0011 0010

 

0001 1001

 

 

 

 

26

0011 0100

 

0001 1010

 

 

 

 

27

0011 0110

 

0001 1011

 

 

 

 

28

0011 1000

 

0001 1100

 

 

 

 

29

0011 1010

 

0001 1101

 

 

 

 

30

0011 1100

 

0001 1110

 

 

 

 

31

0011 1110

 

0001 1111

 

 

 

 

Use of address 0 is not recommended on a Modbus/Unitelway network as this address has the effect of deactivating the option card.