3. Implementation of the communication option cards

3. 10. 10. Communication fault

Ethernet communication faults are indicated by the red FLT LED on the card.

Parameter [Network fault] (CnF-)can be used to obtain more detailed information about the origin of the fault. It can only be accessed on the graphic display terminal, in the [1.10 DIAGNOSTICS] (dGt-)menu, [MORE FAULT INFO] (AFI-).

Value Description of the values of the [Network fault] (CnF-)parameter

0No fault

Tcp/Modbus Time out fault.

The Tcp/Modbus Time out is activated as soon as the control word is received:

1- If no IP master has been configured, the period of activity is maintained by receipt of the control word.

- If an IP master has been configured, the period of activity is maintained by any type of Tcp/Modbus request on this IP address.

No Time out is managed if its value equals 0.

10Ethernet network overload

11No signal from the Ethernet network, cable pulled out, etc.

3.10. 11. FDR service fault (EPF2)

The EPF2 communication fault is indicated by the red RD LED on the card.

This fault appears when a problem arises during the FDR status diagram sequence on the drive, provided that the FDR service is being used and that FDR errors are permitted on the drive ([FDR Error Mgt.] (FdrG) = [Yes] (YES) or FDR file error (address 60 060) = [Yes] (YES)). This fault is resettable.

The EPF2 fault is also triggered if the drive IP address is already being used by another device. In this case, the EPF2 fault is not resettable. You should then modify the drive IP address, or that of the device using this IP address, then restart the drive.

It is possible to obtain more detailed information about the origin of the fault. It can only be accessed on the graphic display

terminal, in the [1.9 COMMUNICATION] (COM-)menu, [Ethernet] (EtH-),[FDR fault] (Fdrd).

Value Description of the values of the [Network fault] (CnF-)parameter

2FDR configuration file incompatible

3Error reading the FDR file

4Error writing the FDR file

7Time out for access to the FTP server has elapsed. This time out cannot be set (90 s)

9Duplication of the IP address

12

FDR file not present in the FTP server

65

Page 65
Image 65
Schneider Electric ATV61 manual Communication fault, FDR service fault EPF2