3. Implementation of the communication option cards

Configuring the "IO Scanner" page using TCP/Modbus messaging

Using TCP/Modbus services and calling on the Ethernet card’s Modbus server, assign the same drive parameter as for the Altivar 38 register to each periodic register.

The table below represents the default table for the Altivar 38 periodic data as seen by the PLC module.

Ethernet

Description

ATV61 register

server

and address

address

 

 

 

 

50 001

Output periodic

CMD

8 501

no. 1

 

 

 

 

 

 

 

50 002

Output periodic

LFRD

8 602

no. 2

 

 

 

50 003

Output periodic

CMI

8 504

no. 3

 

 

 

50 004

Output periodic

IOLR

0 478

no. 4

 

 

 

 

 

 

 

50 005

Output periodic

--

0 000

no. 5

 

 

 

50 006

Output periodic

--

0 000

no. 6

 

 

 

50 007

Output periodic

--

0 000

no. 7

 

 

 

 

 

 

 

50 008

Output periodic

--

0 000

no. 8

 

 

 

50 009

Output periodic

--

0 000

no. 9

 

 

 

50 010

Output periodic

--

0 000

no. 10

 

 

 

 

 

 

 

Ethernet

Description

ATV61 register

server

and address

address

 

 

 

 

50 017

Input periodic

ETA

3 201

no. 1

 

 

 

 

 

 

 

50 018

Input periodic

RFRD

8 604

no. 2

 

 

 

50 019

Input periodic

LCR

3 204

no. 3

 

 

 

50 020

Input periodic

IOLR

0 478

no. 4

 

 

 

 

 

 

 

50 021

Input periodic

AI1R

5 232

no. 5

 

 

 

50 022

Input periodic

OTR

3 205

no. 6

 

 

 

50 023

Input periodic

DF1

7 101

no. 7

 

 

 

 

 

 

 

50 024

Input periodic

ETI

3 206

no. 8

 

 

 

50 025

Input periodic

--

0 000

no. 9

 

 

 

50 026

Input periodic

--

0 000

no. 10

 

 

 

 

 

 

 

We recommend that you use the configuration presented above due to the fact that neither PowerSuite nor the pages of the drive standard HTTP server offer the Altivar 38 parameter addresses during configuration of the periodic parameter assignment table for the Altivar 61’s VW3 A3 310 Ethernet card.

If the Altivar 38’s VW3 A58310 Ethernet card uses one or more periodic parameters alongside those that are configured by default (modification of factory settings):

Using the PowerSuite software workshop, pages of the drive standard HTTP server or TCP/Modbus services, you should modify the configuration of the periodic parameter assignment table for the Altivar 61’s VW3 A3 310 Ethernet card so that it has exactly the same configuration as that of the Altivar 38 (see previous section).

Parameter incompatibilities

When the IO Scanner is configured via the HTTP server or PowerSuite, the register’s Altivar 61 logic address is displayed, but only the description matters to you.

No modification should be made in the PLC when the IO Scanner function is being used.

Altivar 38 PKW parameter-setting service

In "ATV38 Interchangeability" mode (SE8 mode), we recommend use of the Altivar 38’s PKW parameter-setting service as described in the Altivar 38 VW3 A58310 Ethernet card User’s Manual.

Note: Both these services use the same PKE, R/W and PWE output variables (output registers 28, 29 and 31), as well as the same PKE, R/W/N and PWE input variables (input registers 28, 29 and 31) of the Altivar 38.

SNMP agent

The following modifications apply to the Altivar 61’s VW3 A3 310 Ethernet card:

"SysName" object: This object took the name of the Ethernet card in the case of the Altivar 38 ("VW3A58310"), whereas it now takes the name of the Altivar 61, if it exists.

"SysService" object: Value equals -1 in the case of the Altivar 38, as against 72 with the Altivar 61.

Use of a "community name": the "community string" character string in read/write mode for the Altivar 61 is "schneider"; "public" in read-only mode.

For the Altivar 38, it was: PRIVATE

68

Page 68
Image 68
Schneider Electric ATV61 manual Configuring the IO Scanner page using TCP/Modbus messaging, Snmp agent