The MSTR Instruction

3.2.10Reset Option Module MSTR Operation

The Reset Option Module operation (type 10 in the displayed register of the top node) causes a Quantum web embedded server module to enter a reset cycle to reset its operational environment.

Control Block

The registers in the MSTR control block (the top node) contain the Reset Option

Utilization

Module information as described in the following table:

 

 

 

 

 

Register

Function

Content

 

 

 

 

 

Displayed

Operation Type

10

 

 

 

 

 

First implied

Error status

Displays a hex value indicating an MSTR error,

 

 

 

when relevant.

 

 

 

 

 

Second implied

Not applicable

 

 

 

 

 

 

Third implied

Not applicable

 

 

 

 

 

 

Fourth implied

Low byte

Quantum backplane slot address of the web

 

 

 

embedded server module.

 

 

 

 

 

Fifth ... Eighth

Not applicable

 

 

implied

 

 

 

 

 

 

3.2.11Read CTE (Config Extension Table) MSTR Operation

The Read CTE operation (type 11 in the displayed register of the top node) reads a given number of bytes from the Ethernet configuration extension table to the indicated buffer in PLC memory. The bytes to be read begin at a byte offset from the beginning of the CTE. The content of the Ethernet CTE table is displayed in the middle node of the MSTR block.