Installing and Configuring the Module
2.5Configuring the Module with Concept
Once the Ethernet web embedded server module has been installed in the backplane and you have consulted your network administrator about whether to change the IP address or framing or to specify a gateway or subnet mask:
1.Open the Concept project without connecting to the controller. The controller and I/O should be configured.
2.Set the number of Ethernet modules in the configuration extension.
3.Enter each Ethernet module in the I/O map.
4.Fill in the parameter dialog box for each Ethernet module.
Figure 15 Parameter Dialog for an Ethernet Web Embedded Server Module
5.Save the project.
6.Connect to the controller.
7.Open the online control panel. Clear the existing configuration of the controller.
8.Download the project, including the configuration, to the controller. Do not start the controller. Leave the dialog open.
9.Reset the Ethernet web embedded server module in the backplane (hot swap). Wait until the Link indicator lights.
10.Start the controller. This will close the dialog box.
24 | 840 USE 115 00 Version 1.0 |