Schneider Optics Modicon Quantum Ethernet manual Hex Error Code Meaning, Ss Hex value Meaning

Models: Modicon Quantum Ethernet

1 105
Download 105 pages 29.91 Kb
Page 39
Image 39

 

 

The MSTR Instruction

 

 

 

 

 

 

 

Hex Error Code

Meaning

 

 

 

 

1001

User has aborted the MSTR element.

 

 

 

 

2001

An unsupported operation type has been specified in the control block.

 

 

 

 

2002

One or more control block parameters has been changed while the

 

 

MSTR element is active (applies only to operations that take multiple

 

 

scans to complete). Control block parameters may be changed only

 

 

when the MSTR element is not active.

 

 

 

 

2003

Invalid value in the length field of the control block.

 

 

 

 

2004

Invalid value in the offset field of the control block.

 

 

 

 

2005

Invalid values in the length and offset fields of the control block.

 

 

 

 

2006

Invalid slave device data area.

 

 

 

 

3000

Generic Modbus fail code.

 

 

 

 

30ss*

Modbus slave exception response.

 

 

 

 

4001

Inconsistent Modbus slave response.

 

 

 

 

F001

Option Module not responding

 

 

 

* The ss subfield in error code 30ss is shown in the following table.

ss Hex value

Meaning

 

 

01

Slave device does not support the requested operation.

 

 

02

Nonexistent slave device registers requested.

 

 

03

Invalid data value requested.

 

 

04

 

 

 

05

Slave has accepted long-duration program command.

 

 

06

Function can’t be performed now; a long-duration command is

 

in effect.

 

 

07

Slave rejected long-duration program command.

 

 

An error on the TCP/IP Ethernet network itself may produce one of the following errors in the MSTR control block:

Hex Error Code

Meaning

 

 

5004

Interrupted system call.

 

 

5005

I/O error.

 

 

5006

No such address.

 

 

5009

The socket descriptor is invalid.

 

 

500C

Not enough memory.

 

 

500D

Permission denied.

 

 

5011

Entry exists.

 

 

840 USE 115 00 Version 1.0