Scotsman Ice C1030, C0522, C0530, C0830, C0630 user manual Precharged Line Routing

Models: C0630 C1030 C0830 C0530 C0522

1 28
Download 28 pages 53.84 Kb
Page 13
Image 13
Precharged Line Routing

C0522 through C1030

Remote Condenser Models - User Manual

Precharged Line Routing

Do not connect the precharged tubing until all routing and forming of the tubing is complete. See the Coupling Instructions for final connections.

1.Each set of pre-charged tubing lines contains a 3/8” diameter liquid line, and a 1/2” diameter discharge line. Both ends of each line have quick connect couplings, the end without access valves goes to the ice maker.

Note: The openings in the building ceiling or wall, listed in the next step, are the minimum sizes recommended for passing the refrigerant lines through.

2.Have the roofing contractor cut a minimum hole for the refrigerant lines of 1 3/4”. Check local codes, a separate hole may be required for the electrical power supply to the condenser.

Caution: Do NOT kink the refrigerant tubing while routing it.

3.Route the refrigerant tubes thru the roof opening. Follow straight line routing whenever possible. Excess tubing may EITHER be coiled up INSIDE the building OR cut out prior to connection to the ice maker and condenser.

If the excess tubing is cut out, after re-brazing the tubing must be evacuated prior to connection to the ice maker or condenser.

If the excess tubing is to be coiled, spiral it horizontally to avoid excess trapping in the lines.

5.Have the roofing contractor seal the holes in the roof per local codes

Minimize

Outdoor

Tubing

Keep Excess

Tubing Within

Conditioned

Space

July 2006

Page 11

Page 13
Image 13
Scotsman Ice C1030, C0522 Precharged Line Routing, Minimize Outdoor Tubing Keep Excess Tubing Within Conditioned Space