![Precharged Line Routing](/images/new-backgrounds/65975/6597525x1.webp)
C0522 through C1030
Remote Condenser Models - User Manual
Precharged Line Routing
Do not connect the precharged tubing until all routing and forming of the tubing is complete. See the Coupling Instructions for final connections.
1.Each set of
Note: The openings in the building ceiling or wall, listed in the next step, are the minimum sizes recommended for passing the refrigerant lines through.
2.Have the roofing contractor cut a minimum hole for the refrigerant lines of 1 3/4”. Check local codes, a separate hole may be required for the electrical power supply to the condenser.
Caution: Do NOT kink the refrigerant tubing while routing it.
3.Route the refrigerant tubes thru the roof opening. Follow straight line routing whenever possible. Excess tubing may EITHER be coiled up INSIDE the building OR cut out prior to connection to the ice maker and condenser.
If the excess tubing is cut out, after
If the excess tubing is to be coiled, spiral it horizontally to avoid excess trapping in the lines.
5.Have the roofing contractor seal the holes in the roof per local codes
Minimize
Outdoor
Tubing
Keep Excess
Tubing Within
Conditioned
Space
July 2006
Page 11