Scotsman Ice C1030 Product Description and Electrical Requirements, Central Condenser Coils

Models: C0630 C1030 C0830 C0530 C0522

1 28
Download 28 pages 53.84 Kb
Page 8
Image 8
Product Description and Electrical Requirements

C0522 through C1030

Remote Condenser Models - User Manual

Product Description and Electrical Requirements

Dimensions

Model

Electrical

Use condenser

Minimum Circuit

Maximum

w” x d” x h”

Ampacity

Fuse Size*

 

 

 

22.75*** x 24 x 23

C0522SR-1

115/60/1

ERC111-1

14.9

15

same

same

same

ERC211-1**

14.9

15

30.75*** x 24 x 23

C0530SR-1

115/60/1

ERC111-1

14.9

15

 

 

 

 

 

 

same

same

same

ERC211-1**

14.9

15

same

C0630SR-32

208-230/60/1

ERC311-32

18

20

30.75*** x 24 x 29

C0830SR-32

208-230/60/1

ERC311-32

10

15

same

C0830SR-3

208-230/60/3

ERC311-32

8.2

15

same

C1030SR-32

208-230/60/1

ERC311-32

15.6

20

same

C1030SR-3

208-230/60/3

ERC311-32

10.8

15

 

 

 

 

 

 

*Or HACR circuit breakers.

**ERC211 has two circuits, when two C0522s or C0530s are connected to it, fan motor relay kit KCMR120 must be used to control the fan motor.

***Maximum width at top panel.

Ratings include the remote condenser motor, as it is designed to be powered by the ice machine. If connecting remote condenser independently of the ice machine, use the information on the condenser's dataplate for fuse and wire sizes.

Table notes: Medium cube models have the same electrical characteristics as Small. Series revision code omitted. All the listed condensers include a headmaster valve.

Central Condenser Coils

The ice machine may be connected to a central condenser coil. The requirements are:

Coil – not previously used with mineral oil system. Virgin coil preferred.

Correct size (internal volume) and capacity (BTUH).

Includes a headmaster valve for discharge pressure control. Headmaster kit available for certain MAC condensers, kit number is RCKCME6GX.

Fan motor on all the time or controlled to be on whenever the ice machine is operating.

Precharged tubing kits:

The ice making head’s and the remote condenser’s refrigeration circuits must be connected. They are designed to be connected using precharged refrigerant tubing, supplied in kits of liquid and discharge tubes. Several lengths are available, order the one that just exceeds the length needed for the site.

10”

20’

40’

75’

RTE10

RTE20

RTE40

RTE75

 

 

 

 

 

 

 

 

No additional refrigerant is required.

Note: Refrigerant charge is supplied with the ice machine.

July 2006

Page 6

Page 8
Image 8
Scotsman Ice C1030 Product Description and Electrical Requirements, Central Condenser Coils, Precharged tubing kits, RTE10