Scotsman Ice SCN60 Component Diagnostics, Membrane Switch, Pump Switch - Pump model only

Models: SCN60

1 37
Download 37 pages 22.84 Kb
Page 27
Image 27
Component Diagnostics

SCN60

Service

Component Diagnostics

Membrane Switch

Pump Switch - Pump model only

Unplug and check connector pins (left side is pin 1), read about 10 ohms when activating the button, and OL when not pressing the button: Pin 2-3 On/Off Switch; 4-3 Clean Reset Switch

Compressor

Check temperature of compressor, if very hot, add access valves to refrigeration system and check system pressures. If very low, add very small amount of R-134a. If pressure does not improve, capillary tube may be restricted. If pressures improve find and correct refrigerant leak.

If compressor temperature is normal and compressor is drawing high amps, check start relay.

If relay is good and compressor is not overheating but drawing high amps, replace compressor.

The pump switch activates the pump based on pressure to it from water inside the drain hose to the pump inlet. It is normally open. When pressure increases the switch closes, turning on the pump motor until the pressure falls.

The safety switch (the red one) is normally closed and operates at a higher activation pressure than the pump switch. It stops operation of the machine if it opens.

Ice Level Sensor

To operate, the unit must have:

Power to the controller

Water sensed

Call for ice

With power on and Ice Making light on, check sensor connector, if secure and the unit not operating, remove connector and jump the two middle pins at J9 on the controller together. Unit should start. If it does, replace the sensor, if not, replace the controller.

Membrane Switch Auger

Pump Switch - Pump model only Comp

May 2011 Page 11

Page 27
Image 27
Scotsman Ice SCN60 Component Diagnostics, Membrane Switch, Pump Switch - Pump model only, Compressor, Ice Level Sensor