Digital Modules

4-7

S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07
4.3.1 Parameters of the Digital Input Modules

The parameterized digital input modules use a subset of the parameters and

ranges of values listed in the table below, depending on functionality. Refer to the

section on a particular digital module, starting from Section 4.7, to find out which

subset it is capable of using.

Don’t forget that some digital modules have different time delays after parameter

assignment.

The default settings apply if you have not performed parameter assignment in
STEP 7.
Table 4-6 Parameters of the Digital Input Modules
Parameter Value Range Default2Parameter
Type Scope
Enable
Diagnostic interrupt1)
Hardware interrupt1) Yes/no
Yes/no No
No Dynamic Module
Destination CPU for
interrupt 1 to 4 Static Module
Diagnostics
Wire break
No load voltage
L+/sensor supply
Yes/no
Yes/no No
No Static Channel
Trigger for hardware
interrupt
No
Dynamic
Channel
Rising (positive) edge
Falling (negative) edge
Yes/no
Yes/no
No
No Dynamic Channel
Input delay 0.1 ms (DC)
0.5 ms (DC)
3 ms (DC)
20 ms (DC/AC)
3 (DC) Static Channel
Reaction to error Substitutea value (SV)
Keep last value (KLV) SV Dynamic Module
Substitute“1” Yes/no No Dynamic Channel
1) If you use the module in ER-1/ER-2, you must set this parameter to “No” because the interrupt lines are
not available in ER-1/ER-2.
2) Only in the CC (central controller) is It possible to start up the digital modules with the default settings and
without HWCONFIG support.