Analog Modules
5-134 S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07
Operational limit (in the entire temperature range, with
reference to the input range)
Voltage input " 0.3 %
Current input " 0.5 %
Thermocouple Type B " 3.5 C
Type N " 2.7 C
Type E " 1.8 C
Type R " 3.3 C
Type S " 3.2 C
Type J " 2.4 C
Type L " 1.7 C
Type T " 0.8 C
Type K " 2.5 C
Type U " 1.2 C
Basic error (operational limit at 25 C, referred to input
range)
Voltage input " 0.05 %
Current input " 0.15 %
Thermocouple Type B " 0.9 ���C
Type N " 0.7 C
Type E " 0.5 C
Type R " 0.9 C
Type S " 0.8 C
Type J " 0.6 C
Type L " 0.4 C
Type T " 0.2 C
Type K " 0.6 C
Type U " 0.3 C
Temperature error (with
reference to the input
range)
" 0.015%/K
Linearity error (with
reference to the input
range)
" 0.15%
Repeatability (in steady
state at 25 C, with
reference to the input
range)
" 0.15%
Status, Interrupts, Diagnostics
Interrupts
Hardware interrupt Parameters can be
assigned
Diagnostic Interrupt Programmable
Diagnostic functions Programmable
Group error display
For internal fault
For external fault
Programmable
Red LED (INTF)
Red LED (EXTF)
Diagnostic information
can be displayed Yes
Data for Selecting a Sensor
Input range (rated
values)/Input resistance
Voltage " 25 mV
" 50 mV
" 80 mV
"100 mV
"250 mV
"500 mV
" 1 V
" 2.5 V
" 5 V
" 10 V
>2 M
>2 M
>2 M
>2 M
>2 M
>2 M
>2 M
>2 M
>2 M
>2 M
Current " 25 mA /50
Thermocouple Types B, N,
E, R, S, J, L,
T, K, U
>2 M
Maximum input voltage for
voltage input (destruction
limit)
35 V continuous;
75 V for max. 1 s
(duty factor 1:20)
Maximum input current for
current input (destruction
limit)
32 mA
Connection of the sensor
For measuring voltage Possible
For measuring current
As four-wire transmitter Possible
Characteristic linearization
For thermocouples Types B, N, E, R, S, J, L,
T, K, U
Temperature compensation Yes, programmable
Internal temperature
compensation Possible
Unit for temperature
measurement Degrees Celsius; degrees
Fahrenheit