Interface Submodules
13-52 S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07
13.7.11 Analog Value Representation for the Measuring Ranges of theAnalog Outputs

Voltage and Current Output Ranges

Table 13-44 contains the representation of

The voltage output range ± 10 V and

The current output range ± 20 mA.

Table 13-44 Representation of the Analog Output Ranges (Voltage and Current Output Ranges)
Range
Units Output Range Output Range
Range Decimal Hexadecimal "10 V "20 mA
Overflow ≥(32512 ≥(7F00H11.851 V
Overrange
32496
:
27664
7EF0H
:
6C10H
11.7534 V
:
10.0005 V
Nominal range
27648
:
0
:
-27648
6C00H
:
0H
:
9400H
10 V
:
0 V
:
-10 V
20 mA
:
0 mA
:
-20 mA
Underrange
-27664
:
-32512
93F0H
:
8100H
-10.0005 V
:
-11.759 V
Underflow -32528 ≤(80F0H-11.851 V