PROFIBUS DP Master Interface IM 467/IM 467 FO

8-13

S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07
8.4.2 Technical Specifications of the IM 467 FO

6ES7 467-5FJ00-0AB0

Dimensions and Weight
Dimensions
W x H x D (mm)
Weight
25 x 290 x 210
700 g
PROFIBUS DP
Standard
Transmission rate
Transmission
technology
PROFIBUS DP,
EN 50 170
9.6 kbps to 12 Mbps,
parameterizable in steps (3
Mbps and 6 Mbps not
possible)
FOC
Wavelength l = 660 nm 2 x
Duplex socket
Current consumption
Current consumption from
the S7-400 bus (24 VDC)
The IM does not consume
any current at 24 V, and it
only makes this voltage
available at the MPI/DP
interface.
Total current consumption
of the components
connected to the DP
interfaces, with a maximum
of
150 mA
PROFIBUS DP
Conditions of Use
Can be used in SIMATIC S7-400, max. 4
IM 467 in the central
controller
IM 467 cannot be used with the CP 443-5
Supply voltage 5 VDC via the backplane
bus
Current consumption
From 5 VDC
1.3 A
Addressing range Max. 4 KB for inputs and 4
KB for outputs
DP master Yes
DPV 1 No
Enable/disable No
Number of connectable I/O
devices
(slaves)
96
Number of connections for
S7 functions for the
programming device and
operator control and
monitoring
32 + 1 diagnostic
connection
Data volume per slave Max. 244 bytes
Consistency Max. 128 bytes
Configuration software STEP 7
DP slave No
Deviations from the DP Interface Integrated
in the CPU
Different SSL IDs for system diagnostics
Possibly extended SFC run times
Additional return codes for SFC 14 and
SFC 15