Analog Modules
5-81
S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07
Basic error (operational limit at 25 °C, referred to input
range)
Voltage input
" 80 mV
" 250 mV
" 500 mV
" 1 V
" 2.5 V
" 5 V
1 V to 5 V
" 10 V
" 0.17%
" 0.15%
" 0.15%
" 0.15%
" 0.15%
" 0.15%
" 0.15%
" 0.15%
Current input
0 mA to 20 mA
" 20 mA
4 ... 20 mA
" 0.15%
" 0.15%
" 0.15%
Resistance test
0 to 48 ;
four-conductor
measurement
" 0.15%
0 to 150 ,
four-conductor
measurement
" 0.15%
0 to 300 
four-conductor
measurement
" 0.15%
0 to 600 ;
four-conductor
measurement
" 0.15%
0 to 5000 ;
four-conductor
measurement (in
the range of
6000 )
" 0.15%
0 to 300 ;
three-conductor
measurement
" 0.3%
0 to 600 ;
three-conductor
measurement
" 0.3%
0 to 5000 Ω;
three-conductor
measurement (in
the range of
6000 )
" 0.3%
Thermocouples
TC type B
TC type R
TC type S
TC type T
TC type E
TC type J
TC type K
TC type U
TC type L
TC type N
" 8.2 K
" 5.2 K
" 5.9 K
" 1.2 K
" 1.8 K
" 2.3 K
" 3.4 K
" 1.8 K
" 2.3 K
" 2.9 K
Resistance thermocouples, four-conductor
standard measuring range
Pt 100
Pt 200
Pt 500
Pt 1000
Ni 100
Ni 1000
" 2.0 K
" 2.5 K
" 2.0 K
" 1.6 K
" 0.4 K
" 0.4 K
Climatic measuring range
Pt 100
Pt 200
Pt 500
Pt 1000
Ni 100
Ni 1000
" 0.2 K
" 0.2 K
" 0.2 K
" 0.2 K
" 0.4 K
" 0.4 K
Resistance thermocouples, three-conductor
standard measuring range
Pt 100
Pt 200
Pt 500
Pt 1000
Ni 100
Ni 1000
" 3.1 K
" 4.9 K
" 3.9 K
" 3.1 K
" 0.8 K
" 0.8 K
Climatic measuring range
Pt 100
Pt 200
Pt 500
Pt 1000
Ni 100
Ni 1000
" 0.4 K
" 0.4 K
" 0.4 K
" 0.4 K
" 0.8 K
" 0.8 K
Temperature error (with
reference to the input range) " 0.004% K
Linearity error (with reference
to the input range) " 0.01% K
Repeat accuracy (in the steady
state at 25 °C, referred to the
input range)
" 0.1%