Analog Modules
5-84 S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07
Table 5-51 Parameters of the SM 431; AI 8 14 Bit, continued
Parameter ScopeParameter
Type
Default1
Value Range
Interference
suppression 60 Hz; 50 Hz 50 Hz Static Channel
Smoothing None
Low
Average
High
None
Static Channel
Ref. junction None
RTD on Channel 0
Reference temperature value dynamic
None
1Only in the CC (central controller) is it possible to start up the analog modules with the default settings.
Smoothing of the Measured Values

You fill find information that is generally applicable to the smoothing of analog

values in Section 5.6.

The following figure indicates for the module in the case of a step response the

number of module cycles after which the smoothed analog value applies at almost

100%, depending on the smoothing setting. The figure applies to every change of

signal at an analog input.

50
100
0
63
50 100 150 200
Smoothing: low:
average:
high:
Module cycles
Signal variation
in percent
Step response for any analog input signal
Figure 5-29 Step Response of the SM 431; AI 8 14 Bit