Analog Modules
5-80 S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07
Suppression of Interference, Limits of Error
Interference voltage suppression for f = nx (f1 "1%),
(f1 = interference frequency) n = 1, 2, ...
Common-mode
interference
(UCM < 120 Vss)
> 100 dB
Series-mode interference
(peak value of interference
< rated value of input
range)
> 40 dB
Crosstalk between the inputs >70 dB
Operational limit (in the entire temperature range, with
reference to the input range)
Voltage input
" 80 mV
" 250 mV
" 500 mV
" 1 V
" 2.5 V
" 5 V
1 V to 5 V
" 10 V
" 0.38%
" 0.35%
" 0.35%
" 0.35%
" 0.35%
" 0.35%
" 0.35%
" 0.35%
Current input
0 ... 20 mA
" 20 mA
4 mA to 20 mA
" 0.35%
" 0.35%
" 0.35%
Resistance test
0 to 48 ;
four-conductor
measurement
" 0.35%
0 to 150 ,
four-conductor
measurement
" 0.35%
0 to 300 
four-conductor
measurement
" 0.35%
0 to 600 ;
four-conductor
measurement
" 0.35%
0 to 5000 ;
four-conductor
measurement (in
the range of
6000 )
" 0.35%
0 to 300 ;
three-conductor
measurement
" 0.5%
0 to 600 ;
three-conductor
measurement
" 0.5%
0 to 5000 Ω;
three-conductor
measurement (in
the range of
6000 )
" 0.5%
Thermocouples
TC type B
TC type R
TC type S
TC type T
TC type E
TC type J
TC type K
TC type U
TC type L
TC type N
" 14.8 K
" 9.4 K
" 10.6 K
" 2.2 K
" 4,0 K
" 5.2 K
" 7.6 K
" 3.5 K
" 5.1 K
" 5.5 K
Resistance thermocouples, four-conductor
standard measuring range
Pt 100
Pt 200
Pt 500
Pt 1000
Ni 100
Ni 1000
" 4.6 K
" 5.7 K
" 4.6 K
" 3.7 K
" 0.9 K
" 0.9 K
Climatic measuring range
Pt 100
Pt 200
Pt 500
Pt 1000
Ni 100
Ni 1000
" 0.5 K
" 0.5 K
" 0.5 K
" 0.5 K
" 0.9 K
" 0.9 K
Resistance thermocouples, three-conductor
standard measuring range
Pt 100
Pt 200
Pt 500
Pt 1000
Ni 100
Ni 1000
" 5.2 K
" 8.2 K
" 6.5 K
" 5.2 K
" 1.3 K
" 1.3 K
Climatic measuring range
Pt 100
Pt 200
Pt 500
Pt 1000
Ni 100
Ni 1000
" 0.7 K
" 0.7 K
" 0.7 K
" 0.7 K
" 1.3 K
" 1.3 K