Analog Modules
5-144 S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07
Repeat accuracy (in the steady
state at 25 °C, referred to the
output range)
" 0.05%
Output ripple; band width 0 to
50 kHz (with reference to the
output range)
" 0.05%
Status, Interrupts, Diagnostics
Interrupts None
Diagnostic functions None
Substitute value can be applied No
Data for Selecting an Actuator
Output ranges (rated values)
Voltage " 10 V
0 V to 10 V
1 V to 5 V
Current " 20 mA
0 mA to 20 mA
4 mA to 20 mA
Load resistance (in the nominal
range of the output)
For voltage outputs Min. 1 k
capacitive load Max. 1 F
For current outputs Max. 500
00 with reduced
UCM to < 1 V
Inductive load Max. 1 mH
Voltage outputs
Short-circuit protection Yes
Short-circuit current Max. 30 mA
Current outputs
No-load voltage Max. 19 V
Destruction limit for voltages/
currents connected from
outside
Voltage at outputs to MANA Max. 20 V continuous
75 V for 1 ms (cycle
factor 1 : 20)
Current Max. 40 mA
continuous
Connection of actuators
For voltage output
– Two-conductor
connection Possible, without
compensation for
circuit resistance
– Four-conductor
connection
(measuring circuit)
Possible
For current output
– Two-conductor
connection Possible