Analog Modules
5-40 S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07
5.7.1 Parameters of the Analog Input Modules

The analog input modules use a subset of the parameters and ranges of values

listed in the table below, depending on the functionality. Refer to the section on the

module concerned, starting from Section 5.18, to find out which subset the module

is capable of using.

The default settings apply if you have not performed parameter assignment in
STEP 7.
Table 5-42 Parameters of the Analog Input Modules
Parameter Value Range Default2) Parameter
Type Scope
Enable
Diagnostic interrupt1)
Hardware interrupt1)
Yes/no
Yes/no
No
No Dynamic Module
Destination CPU for
interrupt 1 to 4 Static Module
Trigger for hardware
interrupt
End of scan cycle
reached at input Yes/no No Static Channel
High limit
Low limit
Constraint possible due to measuring
range
32511 to – 32512
– 32512 to 32511
Dynamic Channel
Diagnostics
Wire break
Reference channel
error
Underflow
Overflow
Short circuit to M
Yes/no
Yes/no
Yes/no
Yes/no
Yes/no
No
No
No
No
No
Static Channel