Interface Modules

6-9

S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07
Operator Controls and Indicators of the Receive IM
INTF LED (red) Lights up if a rack number > 21 or = 0 was set.
Lights up if you have changed the rack number under voltage.
EXTF LED (red) Lights up in the event of an external fault (line fault, for example, if
the terminator is not inserted or if a module has not yet completed
the initialization process).
DIP switch DIP switch to set the number of the mounting rack.
Socket for external
backup voltage
EXT.BATT.
On the IM 461-0 (order number 6ES7461-0AA00-0AA0) you can
connect external backup voltage (5 V to 15 V) or central backup (see
Installation Manual, Chapter 9) to this socket when you want to
replace the mounting rack power supply. This will ensure backup of
the corresponding EU without interruption. If you use this IM in a
cabinet, you should, for reasons of space, use an angled connector
for the incoming supply.
Front connector X1 Upper connector (input) for the connecting cable from the previous
interface module.
Front connector X2 Lower connector (output) for the connecting cable to the next
interface module or for the terminator.
Technical Specifications of the IM 460-0 and IM 461-0
Maximum line length (total) 3 m,
5 m in the IM 461-0 with the order number
6ES7461-0AA01-0AA0, in the IM 461-0 with
the order number 6ES7461-0AA00-0AA0 as of
version A4, in the IM 460-0 with the order
number 6ES7460-1AA01-0AA0 and in the IM
460-0 with the order number
6ES7460-1AA00-0AA0 as of version A5
Dimensions W x H x D (mm) 25 x 290 x 280
Weight
IM 460-0
IM 461-0
600 g
610 g
Current consumption from the S7-400
bus 5 VDC
IM 460-0
IM 461-0
Typ. 130 mA
Max. 140 mA
Typ. 260 mA
Max. 290 mA
Power loss
IM 460-0
IM 461-0
Typ. 650 mW
Max. 700 mW
Typ. 1300 mW
Max. 1450 mW
Terminator 6ES7461-0AA00-7AA0
Backup current No