PROFIBUS DP Master Interface IM 467/IM 467 FO

8-9

S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07

Connector Pin Assignment

The electrical interface used to connect to

PROFIBUS DP (9-pin subminiature D female connector) is specified in the

following table.

1
2
3
4
5
6
7
8
9
PE
RxD/TxD–P
RTS( AG)
M5V2
P5V2
BATT
RxD/TxD–N
Protective earth
Data transfer line – B
Control –A
Data reference potential
Supply plus
Data transfer line – A
yes
yes
yes
yes
––
yes
RUN
RUN
STOP
STOP
INTF
EXTF
Pin
No. Signal Name PROFIBUS DP
Designation
Ass. with
RS 485
Figure 8-4 Connector Pin Assignment
8.3.2 Optical Connection to PROFIBUS DP

Only in the case of 6ES7467-5FJ00-0AB0.

The IM 467 F0 with an integrated fiber-optic cable interface is available for

connecting to the optical version of PROFIBUS DP.

CP443–5
443–5FX00–0XE0
STOP
RUN
INTF
EXTF
RUN
STOP
AUI/TP
X2
34
PROFIBUS FO bus cable
Figure 8-5 Optical Connection to PROFIBUS DP