SED2 AOP Operating Instructions
2.In the Internal mode, scroll through the list of parameter sets until the AOP parameter set appears. Press to confirm the selection.
3.Press again to select All parameters.
4.Use to access the internal AOP parameters. Internal parameters that display AOP information include:
Parameter
P0964
P8552
P8553
P8564
P8560
P8561
Description
Software Version Information
Base slave address
Default baud rate
Enable Autobaud
Battery level
Enable Backlight
Parameter
P8562
P8563
P8564
P8565
P8566
P8567
Description
Free Memory
Enable Text Scrolling
Null USS Responses
USS Timeouts
Parameter Upload (Upread)
CAUTION:
Upload/Download Limitations:
The AOP will normally only upload and download parameters up to and including Level 3. When copying parameter sets between VFDs, you must again complete the quick commissioning to
Do not exit quick commissioning with P3900=1 or all downloaded parameters are reset to their default values.
Memory Limitation:
The delivered AOP supports five European languages: English, German, French, Spanish, and Italian. Due to internal memory limitations, you should delete one of these languages in order to upload the specified ten parameter sets that can be held on the AOP.
To Delete a Language:
Select Language from the main menu, highlight the language you want to delete, and then press and .
NOTE: Once a language has been removed, it cannot be restored.
The upload/upread procedure reads a parameter set from a SED2 VFD and stores that parameter set in the internal memory of the AOP. The AOP can read from a single SED2 VFD in local mode or from one specific SED2 VFD on a network of SED2 VFDs in master mode.
Use the following procedure to upload/upread a parameter set from a SED2 to the AOP:
16 | Siemens Building Technologies |