SED2 AOP Operating Instructions

Quick Commissioning

NOTE: Simultaneously press and , at any time, to display the main menu. The following table describes the main menu items.

Menu Item

Operate

Diagnostics

Parameters

Mode

Upread (upload)

Download

Language

Setup

Timer

Description

Displays the current status of the SED2 VFD/motor.

Displays a recent fault history.

Allows you to select a parameter group (similar to Parameter Filter P0004) and to configure individual parameters.

Allows you to select the AOP mode of operation as follows:

Local

Master

Internal

Slave

PC Mode

Allows you to read a parameter set from a SED2 VFD to the AOP.

Allows you to write a parameter set from the AOP to a SED2 VFD.

Allows you to select a new language for the AOP display.

Allows you to customize the configuration of the AOP.

Allows you to set a start and stop time for SED2 VFD operation.

1.Use and to scroll through the list of options and to highlight the Parameters item. Press to confirm the selection.

The AOP prompts to select the desired parameter group. Use and to scroll through the list of options and to highlight the All parameters item. Press to confirm the selection.

NOTE: AOP Parameters, provides an overview of parameter access levels and a procedure for editing parameters.

2.Use and to scroll through the parameters and to highlight User Access Level P0003. Press to confirm the selection and the cursor advances to the parameter value.

Use and to set P0003=3 (Expert).

Press to confirm the setting and the cursor returns to the parameter.

3.Use and to scroll through the parameters and to highlight Commissioning Parameter P0010. Press to confirm the selection and the cursor advances to the parameter value.

Use and to set P0010=1 (Quick Commissioning).

Press to confirm the setting and the cursor returns to the parameter.

8

Siemens Building Technologies

Page 16
Image 16
Siemens SED2 manual Quick Commissioning, Menu Item, Description