b)It may be necessary to order a transducer longer than the slide adjustment range because of mounting limitations.
c)Ferromagnetic material (a material readily magnetized - such as iron or steel) should be no closer than .25" from the magnet or the rod end. This includes ferrous screws!
d)Transducers longer than 30" may need special supports and split magnets.
e)The rod of the transducer is typically four to five inches longer than the specified length due to “dead zone” and “null zone” areas at the beginning and end of the rod.
f)The cable from the transducer to the OmniLink 5000 should not be run with any high voltage wiring (i.e. 120/240 VAC). In fact, the cable should be run in its own shielded conduit.
g)Read the manufacturers instructions that came with the transducer for other possible issues and mounting considerations.
Section 3.6.4 Linear Transducer Slide Adjust Wiring
A cable must go from the linear transducer mounted on the slide to the
NOTE: The cable should remain unbroken except for the connector in this junction box to keep the shield integrity - do not splice the cable!
Slide adjust motor starters with and without auxiliary contactors are supported by the OmniLink shut height system as are solenoid operated valves for air motor operation. Refer to appendix “B” for typical wiring diagrams. Figures B.7 and B.8 show the wiring for two supported linear transducers. Figures B.9 and B.10 show the wiring of slide adjust motor starters with and without auxiliary contactors. Figure B.11 shows the wiring of a slide adjust air motor.
If you order an OmniLink 5000 control with a slide adjust system, a wiring diagram will be provided as part of the documentation package.
April 17, 2000 Man ual Versio n 1.0 | 3.11 |