SMC Networks 5000 manual Section D.2 Valve Type a Lockout Procedure, Power is on

Models: 5000

1 80
Download 80 pages 31.64 Kb
Page 74
Image 74

Appendix D Lockout Procedure For Air Controlled Systems

Section D.1 General Lockout Considerations

The OmniLink 5000 auto-setup card automatically controls pressures in cushions and counterbalances. Because of this there are special considerations to keep in mind when locking an air system out (at 0 pressure).

Note that cushions can be vented to zero pressure and the press will be allowed to run. A counterbalance that has been vented to zero pressure, however, is considered a stop condition by the press control.

While a type “A” valve has only integrated Fill/Dump valves, the type “B”, and “C” integrated air valves (See Section 3.1 for a discussion of valve types) that Link uses to control air pressure on cushions and counterbalances has a manual as well as an automatic section. The manual section for these valves looks like a typical manual air pressure control with a regulator followed by a check valve. There is a pressure gauge (“G1”) after the regulator but before the check valve, and a gauge (“G2”) at the output air port after the check valve. When raising the pressure by turning the manual regulator “up” the pressure forces the check valve open and gauge “G1” will be approximately equal to gauge “G2”. However when lowering the pressure at the manual regulator, the check valve will prevent the actual output pressure from going down (assuming there are no leaks). A LOX valve on the output is used to blow down the system to lower the pressure. In either case, gauge “G2” shows the true pressure in the counterbalance or cushion.

The automatic section of type “B” and “C” valves (and the only section of type “A” valves) consists of a fill valve and a dump valve. A transducer mounted on the counterbalance surge tank or cushion electronically reports the pressure of the system to the auto-setup board. If the pressure is too low the fill valve puts more air in the system. If the pressure is too high the dump valve vents air to atmosphere.

Section D.2 Valve Type “A” Lockout Procedure

To lock out type “A” valves:

1)Set the air pressure setpoint for the system to 0 psi. This will cause the control to open the dump valve and leave it open to vent the system. Note that this valve will be open only as long as the control is powered. If the system is set to 0 pressure, but the control is turned off before the system can blow down, it will still be pressurized.

2)Use a LOX valve, if present, to dump the air system.

Note!

Step 1 MUST be done even if a LOX valve is opened in step 2 since the

 

control may try to pressurize the system using the Fill/Dump valve if the

 

power is on!

April 17, 2000 Man ual Versio n 1.0

D.1

Page 74
Image 74
SMC Networks 5000 manual Section D.2 Valve Type a Lockout Procedure, Must be done even if a LOX valve is opened in since