State Industries 705 Series 200, U287-084 Flue Terminal Clearances ANS Z21.10.3 CSA

Models: U287-084 705 Series 200

1 40
Download 40 pages 55.25 Kb
Page 25
Image 25

Flue Terminal Clearances (ANS Z21.10.3 ● CSA 4.3)

D

E

B

L

INSIDE

CORNER DETAIL

G

H

A

 

 

I

M

 

 

B

 

 

B

FIXED

K

 

CLOSED

 

 

 

OPERABLE

 

C

B

J

 

 

 

FIXED

B

X AIR SUPPLY INLET

CLOSED

A

OPERABLE

 

 

 

V VENT TERMINAL

F

AREA WHERE

B TERMINAL IS NOT PERMITTTED

Ref

Description

US Installations

 

 

 

A

Clearance above grade, veranda, porch, deck, or balcony

12 inches (30 cm)

 

 

 

B

Clearance to window or door that may be opened

12 inches (30 cm)

 

 

 

C

Clearance to permanently closed window

*

 

 

 

 

Vertical clearance to ventilated soffit, located above the terminal

 

D

within a horizontal distance of 2 feet (61 cm) from the center line

*

 

of the terminal

 

 

 

 

E

Clearance to unventilated soffit

*

 

 

 

F

Clearance to outside corner

*

 

 

 

G

Clearance to inside corner

*

 

 

 

H

Clearance to each side of center line extended above meter/

*

regulator assembly

 

 

 

 

 

I

Clearance to service regulator vent outlet

*

 

 

 

J

Clearance to nonmechanical air supply inlet to building or the

12 inches (30 cm)

combustion air inlet to any other appliance

 

 

 

 

 

K

Clearance to a mechanical air supply inlet

3 feet (91 cm) above if within

10 feet (3 m) horizontally

 

 

 

 

 

L

Clearance above paved sidewalk or paved driveway located on

*

public property

 

 

 

 

 

M

Clearance under veranda, porch, deck, or balcony

*

 

 

 

1A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings.

2Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.

For clearances not specified in ANSI Z223.1/NFPA 54 or CSA B149.1, clearances are in accordance with local installation codes and the requirements of the gas supplier.

305, 505, 705 Indoor Manual

25