Problem

 

Possible cause

 

Corrective action

 

 

 

Leaks in connecting lines.

 

Inspect/replace faulty line or

 

 

 

 

connection.

 

 

 

 

 

 

 

 

Air in circulating lines.

 

Perform venting sequence in

 

 

 

 

Chapter 3.

 

 

 

 

 

 

 

 

Low fluid.

 

Check fluid level in sight glass.

 

 

 

 

Add fluid if required.

 

 

 

 

 

 

 

 

Defective Ful-Flo valve.

See Chapter 3.

 

 

 

Water in fluid.

 

Drain water from low point in

 

Rapid drop in pressure/no

 

 

piping (see Chapter 3), or boil

 

 

 

 

water off.

 

pressure.

 

 

 

 

 

Vent solenoid open.

 

Allow vent timer to run out; or,

 

 

 

 

 

 

 

 

check valve operation when unit

 

 

 

 

 

is cold by opening the fill port.

 

 

 

 

 

Check motor; rewire if

 

 

 

Pump running in reverse.

 

necessary. See electrical

 

 

 

 

 

diagrams.

 

 

 

Pump repair/adjustment needed.

 

Adjust head spacing or replace

 

 

 

 

worn pump components.

 

 

 

 

 

 

 

 

V belt broken/worn.

Replace as required.

 

 

 

Water in fluid.

 

Drain water from low point in

 

Noisy pump.

 

 

piping (see Chapter 3), or boil

 

 

 

 

water off.

 

 

 

Severely degraded fluid.

 

Drain and flush system. Replace

 

 

 

 

fluid.

 

 

 

 

 

Upright Portable Hot Oil TCUs

Chapter 6: Troubleshooting

38

Page 38
Image 38
Sterling 682.88107.00 specifications Problem Possible cause Corrective action