Figure 1
Typical Two-Circuit 60-195 Ton Water Cooled Chiller
Model |
|
|
|
|
| ||
| 60 |
| 75 | 90 |
| 100 | |
|
|
|
| ||||
Cooling Capacity (tons) @ 50°F LWTc | 60.4 |
| 74.9 | 88.8 |
| 102.2 | |
Capacity stages |
|
|
| Infinite | Unloading |
|
|
EER (BTUH/W) |
| 15.2 |
| 15.1 | 15.7 |
| 15.5 |
Nominal water flow (gpm) | Evaporatord | 145 |
| 180 | 213 |
| 245 |
Condenserse | 181 |
| 225 | 266 |
| 307 | |
|
|
| |||||
Condenser connection (no manifold) Flange Conn. (in.) |
| 2.5 |
| 3 | |||
Evaporator manifold connection Victaulic |
| 3 |
| 4 | |||
Amp draw, nameplate | 112 |
| 130 | 138 |
| 170 | |
(460/3/60 V)f |
|
| |||||
|
|
|
|
|
|
| |
Dimensions (in.) | Height |
| 85 |
| 74 | ||
Width |
| 100 |
| 115 | |||
| Depth |
| 45 |
| 72 | ||
Shipping weight (lbs) |
| 3,266 |
| 3,512 | 4,336 |
| 4,982 |
Max operating weight (lbs.) |
| 3,468 |
| 3,754 | 4,594 |
| 5,246 |
cBased on 50ºF (10ºC) chilled water supply temperature and 85ºF (29ºC) tower water. d Based on 2.4 gpm per ton (9.1 lpm per 3.517 kW).
e Based on availability of 85ºF (29ºC) tower water at 25 psi (172.4 kPa/1.7 bars) minimum.
f Multiply 460/3/60 amperage by 2.0 for
Page 12 of 77 | SCW Series Central Chilling Stations |