•No steam, hot air or fume exhausts drawn into the condenser coils.
•Service accessibility.
SCW Series condensing pressure
with 95ºF (35ºC) condenser air
Note: Due to the variables involved in remote
3-11 Checking Motor Direction
Compressor
Check Compressor Rotation Before Starting Unit!
1.Connect a phase monitor and phase incoming power ABC.
2.Connect a refrigerant gauge to the suction service valve. Fully front seat the service valve and open one full turn.
3.Bump start the compressor by switching off then on quickly 0.5 to 1 second. If the rotation is correct, the suction pressure will drop immediately. A rise in pressure will indicate the wrong rotation. If this occurs, change over two electrical phases of the incoming power supply (do not change phase at the compressor starter).
Note:
•Never switch contactor leads or motor leads for reversing rotation.
•Do not use contactor or motor leads for phase matching.
•Compressor damage will occur if the compressor is run in reverse. The compressor motor protector checks for correct phasing and will not allow it to start in reverse.
•If you discover that compressor rotation is reversed, correct it by switching any two main power leads into the disconnect switch or distribution block on the unit.
Water Pump
A positive pressure of 20 to 30 psi (137.9 to 206.8 kPa/1.38 to 2.07 bars) on the TO PROCESS line indicates correct pump rotation.
Page 26 of 77 | SCW Series Central Chilling Stations |