5

Startup Checklists

 

 

5-1 Introduction

Important!

These lists assume the installation information in this manual has been read and followed.

Have new chillers started up and checked by a qualified refrigeration service technician.

Sterling offers factory startup for SCW Series chilling stations.

Call the Sterling Service Department at 1 (800) 233-4819 for more details.

5-2 Water-Cooled SCW Series Startup Checklist

;Check the shipping papers against the serial tag to be sure chiller size, type and voltage is correct for the process.

;Check the transformer primary voltage connections to be sure they are configured for the electrical power you are using.

;The voltage at the main power connection must be within plus or minus ten percent (±10%) of the voltage listed on the serial tag.

;Phase imbalance must be less than two percent (<2%).

;Electrical connections must conform to all applicable codes.

;Complete the chilled water TO PROCESS and FROM PROCESS connections.

;The optional or field installed chilled water supply and return valves on the chiller must be open.

;Be sure the pump tank and chilled water circuit are filled with a water/glycol mixture that provides freeze protection to 20°F (12ºC) below the leaving water temperature you want.

;Complete the tower or city condenser WATER IN and WATER OUT connections. Provide an adequate condenser water supply; 2 gpm per ton for city water or 3 gpm per ton for tower water operation.

;Remove all tools, foreign matter and debris from the pump tank reservoir and piping.

Page 34 of 77

SCW Series Central Chilling Stations

Page 34
Image 34
Sterling installation manual Startup Checklists, Water-Cooled SCW Series Startup Checklist