From Process

The chilled water return for water returning back to the chiller from the process to be cooled and recirculated. Adjust the butterfly valve for the pressure drop that corresponds to the model number of the chiller. Pressure drop is equal to supply pressure minus return pressure

Model

 

Water Side Pressure Drop

 

Number

Condenser (each)

Evaporator (each)

 

Flow (gpm)

PD (psi)

Flow (gpm)

PD (psi)

SCWW/R60

91

4.0

72

5.3

SCWW/R75

102

4.7

90

4.5

SCWW/R90

117

4.4

107

5.6

SCWW/R100

150

5.5

123

3.9

SCWWR115

166

4.3

140

3.0

SCWW/R145

196

4.1

175

4.8

SCWW/R165

219

4.1

200

4.6

SCWW/R195

278

4.7

232

6.0

3-5 Making Tank Piping Connections

If you have purchased the SCW Series central chilling station with the integral pump tank, please proceed with this section.

Return

Bring the chilled water returning from the process to the pump tank warm From Process side. This line is sized according to the flow rate from the process to the pump tank. See Section 3-3 on Page 21 for more information on piping considerations.

Important!

Do not use the SCW Series unit to support piping.

Makeup

Connect a city water source to maintain water level in the pump tank.

Overflow

Connect the OVERFLOW outlet to an approved, trapped drain to permit excess water in the pump tank to overflow to the drain. The overflow line is sized according to the size of the pump tank.

To Drain

Connect to a 1½” line (approx. 63 mm) leading to an approved, trapped drain. You can drain the pump tank if necessary.

SCW Series Central Chilling Stations

Page 23 of 77

Page 23
Image 23
Sterling SCW Series installation manual Making Tank Piping Connections