4-8 High Pressure Cutout
This
High pressure cutout setting
Model | psi | kPa | bars | |
SCW Series | 290 psi | 2,000 kPa | 20 bars | |
chilling stations | ||||
|
|
|
Important!
The high pressure cutout is a manual reset control,
so you should reset it once.
If the problem persists, call a refrigeration service technician
to analyze the problem and to reset the control.
4-9 Low Pressure Cutout
This encapsulated switch safety feature prevents the compressor suction pressure from dropping below a
Model | Opens control circuit @ | Resets control circuit @ | |||||
psi | kPa | bars | psi | kPa | bars | ||
| |||||||
SCW Series | 15 psi | 103.4 kPa | 1.0 bars | 30 psi | 206.9 kPa | 2.1 bars | |
remote | |||||||
|
|
|
|
|
|
4-10 Flow Switch
The flow switch shuts down the chiller if the evaporator water flow falls below a safe operating