4-8 High Pressure Cutout

This electro-mechanical safety feature opens the control circuit if the system condensing pressure exceeds a safe level.

High pressure cutout setting

Model

psi

kPa

bars

SCW Series water-cooled and remote air-cooled

290 psi

2,000 kPa

20 bars

chilling stations

 

 

 

Important!

The high pressure cutout is a manual reset control,

so you should reset it once.

If the problem persists, call a refrigeration service technician

to analyze the problem and to reset the control.

4-9 Low Pressure Cutout

This encapsulated switch safety feature prevents the compressor suction pressure from dropping below a pre-set point. It is factory set to open the control circuit when pressure drops below a safe level. The chiller will restart when the suction pressure reaches 30 psi (206.9 kPa/2.1 bars).

Model

Opens control circuit @

Resets control circuit @

psi

kPa

bars

psi

kPa

bars

 

SCW Series water-cooled and

15 psi

103.4 kPa

1.0 bars

30 psi

206.9 kPa

2.1 bars

remote air-cooled chilling stations

 

 

 

 

 

 

4-10 Flow Switch

The flow switch shuts down the chiller if the evaporator water flow falls below a safe operating gallons-per-minute (liters-per-minute) flow rate.

SCW Series Central Chilling Stations