11.When a dew point fault is generated by the optional dew point controller, the alarm light will activate. The alarm light will flash, indicating a non-critical fault. Press Alarm Reset to deactivate the alarm until the next dew point fault occurs.

12.The top 2 lines of the display show the HEAT and COOL times (in minutes) for the regeneration sequence. Changes to these times can be made by the operator as follows:

a.Press the up or down arrow until the cursor is positioned at the number to be changed.

b.Press the “+” key to increment the number, or the “-“ key to decrement the number.

c.Press the “OK” key to accept the value and write to the relay memory.

OR

d. Press the “ESC” key to cancel the changes.

Note: A change will NOT take effect until step 12-c is done.

13.The dryer is shut off by turning the control power switch to the OFF position.

14.Refer to Schematic drawing A0566087 enclosed in the control enclosure.

Dehumidifying Dryers

Chapter 4: Operation

36 of 59