Sterling SDAA 25-100 specifications Mode Parameter Setting range Default Manf. setting

Models: SDAA 25-100

1 60
Download 60 pages 53.38 Kb
Page 34
Image 34

Entering Operating Parameters to Select Modes

To enter the display:

1.Press both the Up and Down keys for three seconds from the home page. The word SEE will appear in the upper display and PAGE will appear in the lower display.

2.Press the Advance Key to move through the parameter prompts.

3.Press the Up or Down keys to change the parameter value.

4.Press the RESET Key at any time to return to the Home Page display.

Figure 9: Setting List for Redundant Safety Controller (WATLOW), Part No. A0555757

Mode

Parameter

Setting range

Default

Manf. setting

SEn

Sensor Type

0-3

0

-

Lin

Thermocouple Linearization

0-10

0

H (1)

C-F

Temperature Units

Fahrenheit / Celsius

F

-

S.dEC

Temp. Decimal Places

0 – 0.0

0

-

IS.En

INFOSENSE™

Yes / No

No

-

Sc.Lo

Process Scale Low

4.00 to 20.00 mA

4.00 mA

0

 

 

1.00 to 10.00V

1.00V

 

Sc.hi

Process Scale High

4.00 to 20.00 mA

20.00 mA

400

 

 

1.00 to 10.00V

5.00 V

 

CAL

Calibration Offset

-999 to 999

0

-

Ftr.E

Input Filter

Off, DiSP, Cont, both

OFF

-

Ot 1

Output 1 Function

Limit (2)

(2)

-

LSd1

Output 1 Limit Sides

Both, High, Low

Both

High

hyS1

Limit 1 Hysteresis

0.0 to 999.0

1.0

-

Ot2

Output 2 Function

Off / Process Alarm / Limit (2)

OFF

-

LSd2

Output 2 Sides

Both / high / low

Both

-

 

 

None, Process Value, Limit 1 Low Set,

 

 

 

 

Limit 1 High Set, Limit 2 Low Set, Limit

 

 

UdSP

Upper Display Look

2 High Set, Alarm 2 Low Set, Alarm 2

Process

-

 

 

High Set, Limit 3 Low Set, Limit 3 High

 

 

 

 

Set, Alarm 3 Low Set, Alarm 3 High Set

 

 

 

 

None, Process Value, Limit 1 Low Set,

 

 

 

 

Limit 1 High Set, Limit 2 Low Set, Limit

Limit 1

 

LdSP

Lower Display Look

2 High Set, Alarm 2 Low Set, Alarm 2

-

High Set

 

 

High Set, Limit 3 Low Set, Limit 3 High

 

 

 

 

 

 

 

Set, Alarm 3 Low Set, Alarm 3 High Set

 

 

 

 

(0) no lockout, (1) Programming and

 

 

LOC

Lockout

Setup Page Locked, (2) Limit Set

0

2

Points are the only Operation Page

 

 

 

 

 

 

parameters accesible, (3) Full Lockout.

 

 

Dehumidifying Dryers

Chapter 4: Operation

33 of 59

Page 34
Image 34
Sterling SDAA 25-100 specifications Mode Parameter Setting range Default Manf. setting