Sterling SDAA 25-100 specifications Dryer Operation Procedures

Models: SDAA 25-100

1 60
Download 60 pages 53.38 Kb
Page 35
Image 35

4-3 Dryer Operation Procedures

Controller Operation (Without Optional Alarm Horn & Reset Button)

1.Turn the disconnect on the control panel to the ON position. Power is applied to the voltage line fuses, line side of the control power switch and the temperature controller.

2.Turn the control power switch to the ON position. Power is applied to the programmable relay and dew point controller. The valve will move to the start position as follows:

a.The valve motor rotates until the cam switch makes 2 transitions.

b.If the cam switch does not make a transition within 10 seconds, a valve motor fault is generated. “VALVE MTR” is displayed on the relay screen, the alarm light is activated. The valve motor, heaters, and blower shut off.

To restart the dryer, cycle control power to deactivate the alarm light and restart the valve motor sequence.

Note: The relay screen which contains the Alarm Display Messages is located inside the controller enclosure. For a list of Alarm Display Messages, see Page 35.

WARNING! Do not attempt to check the Alarms on the Controller located within the unit enclosure unless you are a qualified electrician!

c.The valve will normally complete one full cycle (revolution).

If the drying process shuts down due to an alarm, the dryer has been setup to have the following operational features:

The bed in process at power-down will remain in process.

The bed in regeneration at power-down will remain in regeneration.

The regeneration timing cycle will restart from the beginning.

Dehumidifying Dryers

Chapter 4: Operation

34 of 59

Page 35
Image 35