Page 23 of 60
4. Touch PUMPS ACTIVE. A keypad pops up.
5. Enter the total number of pumps (1-4) to be controlled by
the system. Use CLR to erase any mistakes. Use ENT
to enter the value. The keypad disappears, and the new
setting appears under PUMPS ACTIVE.
5-2-1-2 Setting Up Alarm Silences
When an alarm occurs, a horn sounds and a strobe light
flashes at each installed central alarm. An alarm banner
appears in the center of the screen. An alarm message and
Silence button are on the banner. Touching this button
silences the horn and turns off the lights for configurable
periods of time and causes the alarm banner to disappear.
You can set different lengths of time for keeping the horn
silent and keeping the light turned off. If a new alarm occurs,
the horn sounds and the light turns on again.
To set the lengths of time for suppressing the alarm strobe
and horn, complete the following steps:
1. Go to the “System Setup” screen by touching the
SYSTEM SETUP button on any screen.
2. On the “System Setup” screen (Figure 4), touch the
STROBE SUPPRESS button. A keypad pops up.
Figure 4: 6” System Setup Screen
3. Enter the number of minutes (between 0 and 99) that you
want the strobe lights to stay off. If you want the light to
stay on as long as the alarm persists, change the setting
to 0. If you want the light to stay off until a new alarm
occurs, enter 99 in the keypad. Use CLR to erase any