Page 42 of 60
5-3-3-2 Transferring Stations to a Standby Pump
If a pump fails, you can transfer all of the controller’s station
assignments for that pump to a standby pump. To do this,
you must disable (take offline) both the source pump and the
standby pump, and the standby pump must have no stations
already assigned to it.
The transfer operation at the controller’s touch screen
merely changes the pump assignment for every station on
the failed pump. It does not transfer any pump settings for
auto shutdown delay, alarms, or blow-back to the standby
pump. Mechanical connections must be changed manually.
To transfer stations from a pump to a standby pump,
complete the following steps:
1. At any screen, touch PUMP STATUS button. The “Pump
Status” screen appears.
2. Both the source pump and the standby pump must be
offline. If either pump is any other state, disable it by
touching its icon briefly. The icon becomes black with a
white outline.
3. Move the vacuum hose from the failed pump to the
standby pump, and carry out any other mechanical
procedures needed to use the standby pump.
4. At the “Pump Status” screen, touch and hold the icon for
any pump until the “Pump Setup” screen appears.
5. At the “Pump Setup” screen, touch Transfer Stations To
Standby Pump. The “Transfer to Standby Pump” screen
opens: