Application Considerations

Application Considerations

Application of this product should be within the cataloged airflow and cooling considerations.

LowAmbient Cooling

The Precedent™ line features, with ReliaTel™ microprocessor controls, low ambient cooling down to 0°F.

Barometric Relief

This product line offers an optional barometric relief damper. for use in conjunction with economizer option. This accessory consists of gravity dampers which open with increased pressure. As the building air pressure increases, the pressure in the unit return air section also increases, opening the dampers and relieving the conditioned space.

NOTE:THE EFFECTIVENESS OF BAROMETRIC RELIEF DAMPER DURING ECONOMIZING OPERATION IS SYSTEM RELATED.

PRESSURE DROP OFTHE RETURN AIR SYSTEM SHOULD BE CONSIDEREDTO CONTROL BUILDING PRESSURIZATION.

Condensate Trap

The evaporator is a draw-thru configuration. A trap must be field provided prior to start-up on the cooling cycle.

Clearance Requirements

The recommended clearances identified with unit dimensions should be maintained to assure adequate service maximum capacity and peak operating efficiency. Actual clearances which appear inadequate should be reviewed with the localTrane sales personnel.

Unit Pitch

These units have reversible sloped condensate drain pans. Units must be installed level, any unit slope must be toward the side of unit where condensate drain is connected.

PKGP-PRC003-EN

11

Page 11
Image 11
Trane PKGP-PRC003-EN manual Application Considerations, LowAmbient Cooling, Barometric Relief, Condensate Trap, Unit Pitch

FAQ

What are the low ambient cooling capabilities of the Precedent line?

The Precedent line features low ambient cooling down to 0F with ReliaTel microprocessor controls.

Is a barometric relief damper available for use with the economizer option?

Yes, this product line offers an optional barometric relief damper for use in conjunction with the economizer option.

What type of configuration does the evaporator have?

The evaporator is a draw-thru configuration, and a trap must be field provided prior to start-up on the cooling cycle.