Trane PKGP-PRC003-EN manual Performance, Data5Ton, Heating Capacities Net WSC60A1 At 2000 CFM

Models: PKGP-PRC003-EN

1 56
Download 56 pages 28.86 Kb
Page 31
Image 31
Table PD-30 — 5 Ton Single Phase

Performance

Data(5Ton)

Table PD-30 — 5 Ton Single Phase

Heating Capacities (Net) WSC60A1 At 2000 CFM

 

 

 

 

 

 

 

Outdoor

InstantaneousHeatingCapacity(Btuh/1000)

 

IntegratedHeatingCapacity(Btuh/1000)

Total Power in Kilowatts at

Temp.

 

at Indicated Indoor Dry Bulb Temp.

 

 

 

at Indicated Indoor Dry Bulb Temp.1

 

 

Indicated Indoor Dry Bulb Temp.

F.

60

70

75

80

 

60

70

75

80

 

60

70

75

80

 

-8

21.4

20.4

20.0

19.7

 

19.3

18.4

18.0

17.7

 

4.44

4.82

5.02

5.22

 

-3

24.3

23.3

22.9

22.6

 

21.9

21.0

20.6

20.3

 

4.53

4.90

5.10

5.31

 

2

27.3

26.3

25.9

25.6

 

24.6

23.7

23.3

23.0

 

4.62

4.99

5.19

5.40

 

7

30.5

29.5

29.0

28.7

 

27.5

26.6

26.1

25.8

 

4.71

5.08

5.28

5.49

 

12

33.8

32.8

32.3

31.9

 

30.4

29.5

29.1

28.7

 

4.81

5.18

5.38

5.59

 

17

37.2

36.2

35.7

35.3

 

33.5

32.6

32.1

31.8

 

4.90

5.28

5.48

5.70

 

22

40.9

39.8

39.2

38.8

 

36.8

35.8

35.3

34.9

 

5.00

5.38

5.58

5.80

 

27

44.6

43.4

42.9

42.3

 

40.1

39.1

38.6

38.1

 

5.10

5.48

5.69

5.92

 

32

48.5

47.2

46.6

46.0

 

43.7

42.5

41.9

41.4

 

5.21

5.59

5.81

6.03

 

37

52.4

51.0

50.4

49.7

 

47.2

45.9

45.4

44.7

 

5.32

5.70

5.92

6.15

 

42

56.3

54.8

54.2

53.4

 

50.7

49.3

48.8

48.1

 

5.43

5.82

6.05

6.28

 

47

60.3

58.8

58.0

57.2

 

60.3

58.8

58.0

57.2

 

5.55

5.95

6.17

6.41

 

52

64.4

62.8

61.9

61.0

 

64.4

62.8

61.9

61.0

 

5.67

6.09

6.31

6.55

 

57

68.5

63.6

65.8

61.7

 

68.5

63.6

65.8

61.7

 

5.81

6.11

6.46

6.56

 

62

69.5

67.6

66.5

65.4

 

69.5

67.6

66.5

65.4

 

5.86

6.27

6.50

6.73

 

67

73.6

71.5

70.4

69.2

 

73.6

71.5

70.4

69.2

 

6.02

6.44

6.67

6.90

 

72

77.7

75.4

74.3

73.1

 

77.7

75.4

74.3

73.1

 

6.19

6.61

6.84

7.08

 

For other airflow conditions, see heating capacity correction factor (Table PD-39).

Net heating capacity and power input includes indoor fan heat at ARI esp. To obtain net heating at other conditions, subtract fan heat at this condition and add fan heat at new condition. Note:

1. Integrated heating capacities and powers include the effects of defrost in the frost region. All heating capacities and power (kw) are at 70% OD relative humidity and demand defrost cycle.

Table PD-31 — 5 Ton Three Phase

Heating Capacities (Net)

 

WSC060A3, A4, AW

At 2000 CFM

 

 

 

 

 

Outdoor

InstantaneousHeatingCapacity(Btuh/1000)

 

 

IntegratedHeatingCapacity(Btuh/1000)

Total Power in Kilowatts at

Temp.

 

at Indicated Indoor Dry Bulb Temp.

 

 

 

 

at Indicated Indoor Dry Bulb Temp.1

 

 

Indicated Indoor Dry Bulb Temp.

F.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

60

70

75

80

60

70

75

80

60

70

75

80

 

-8

21.1

20.1

19.7

19.4

 

19.0

18.1

17.7

17.5

 

4.30

4.69

4.90

5.11

 

-3

24.0

23.0

22.6

22.3

 

21.6

20.7

20.3

20.1

 

4.39

4.78

4.98

5.19

 

2

27.0

26.0

25.8

25.6

 

24.3

23.4

23.2

23.0

 

4.48

4.86

5.06

5.27

 

7

30.3

29.4

29.0

28.8

 

27.3

26.5

26.1

25.9

 

4.57

4.94

5.15

5.35

 

12

33.8

32.8

32.4

32.0

 

30.4

29.5

29.2

28.8

 

4.65

5.03

5.23

5.45

 

17

37.4

36.3

35.8

35.4

 

33.7

32.7

32.2

31.9

 

4.74

5.12

5.32

5.54

 

22

41.1

39.8

39.3

38.9

 

37.0

35.8

35.4

35.0

 

4.83

5.21

5.42

5.64

 

27

44.9

43.5

42.9

42.5

 

40.4

39.2

38.6

38.3

 

4.92

5.31

5.52

5.75

 

32

48.7

47.3

46.7

46.2

 

43.8

42.6

42.0

41.6

 

5.02

5.41

5.63

5.86

 

37

52.5

51.0

50.4

49.8

 

47.3

45.9

45.4

44.8

 

5.12

5.52

5.74

5.97

 

42

56.4

54.8

54.2

53.6

 

50.8

49.3

48.8

48.2

 

5.23

5.63

5.86

6.09

 

47

60.3

58.8

58.1

57.4

 

60.3

58.8

58.1

57.4

 

5.34

5.75

5.98

6.22

 

52

64.4

62.8

62.0

61.3

 

64.4

62.8

62.0

61.3

 

5.46

5.88

6.11

6.35

 

57

68.4

63.6

66.0

61.9

 

68.4

63.6

66.0

61.9

 

5.59

5.90

6.25

6.35

 

62

69.4

67.6

66.7

65.7

 

69.4

67.6

66.7

65.7

 

5.64

6.05

6.28

6.51

 

67

73.5

71.6

70.6

69.6

 

73.5

71.6

70.6

69.6

 

5.79

6.21

6.44

6.68

 

72

77.7

75.7

74.6

73.5

 

77.7

75.7

74.6

73.5

 

5.95

6.38

6.61

6.85

 

For other airflow conditions, see heating capacity correction factor (Table PD-39).

Net heating capacity and power input includes indoor fan heat at ARI esp. To obtain net heating at other conditions, subtract fan heat at this condition and add fan heat at new condition. Note:

1. Integrated heating capacities and powers include the effects of defrost in the frost region. All heating capacities and power (kw) are at 70% OD relative humidity and demand defrost cycle.

PKGP-PRC003-EN

31

Page 31
Image 31
Trane PKGP-PRC003-EN Performance, Data5Ton, Heating Capacities Net WSC60A1 At 2000 CFM, Table PD-31- 5 Ton Three Phase

FAQ

What information is provided in Table PD-30 and Table PD-31?

The tables provide heating capacities and power input for 5 Ton single phase and three phase heat pumps by Trane, including net heating capacity and power input.

What is included in the heating capacities and powers in the tables?

The heating capacities and power kw are at 70% OD relative humidity and demand defrost cycle. They include the effects of defrost in the frost region.

How can I obtain net heating at other conditions?

To obtain net heating at other conditions, subtract fan heat at the current condition and add fan heat at the new condition.