Mechanical Specifications
Factory Installed Options
Black Epoxy
The black epoxy coils have a thermoset vinyl coating that is bonded to the aluminum fin stock prior to the fin- stamping process.The
High Pressure Cutout
This is offered for units that do not have High Pressure cutout as standard. All 3- phase units with scroll compressors include High Pressure Cutout as standard.
Hinged Access Doors
Sheet metal hinges are available on the Filter/Evaporator, Supply Fan/Heat, and the Compressor/Control Access Doors.
Phase Monitor
Phase monitor shall provide 100% protection for motors and compressors against problems caused by phase loss, phase imbalance, and phase reversal. Phase monitor is equipped with an LED that provides an ON or FAULT indicator.
Powered or Unpowered Convenience Outlet
This is a GFCI, 120v/15amp, 2 plug, convenience outlet, either powered or unpowered.When the convenience outlet is powered, a service receptacle disconnect will be available.The convenience outlet is powered from the line side of the disconnect or circuit breaker, and therefore will not be affected by the position of the disconnect or circuit breaker.This option can only be ordered when theThrough the Base Electrical with either the Disconnect Switch or Circuit Breaker option is ordered.
Supply and/or Return Air Smoke Detector
With this option, if smoke is detected, all unit operation will be shut down. Reset will be manual at the unit. Return Air Smoke Detectors require minimum allowable airflow when used with certain models. See the Installation, Operation, and Maintenance (IOM) manual for the models affected and the minimum allowable airflow required.This option is available for microprocessor controlled units.
Through the Base Electrical Access
An electrical service entrance shall be provided allowing electrical access for both control and main power connections inside the curb and through the base of the unit. Option will allow for field installation of
Through the Base Electrical with Circuit Breaker
This option is a thermal magnetic, molded case, HACR Circuit Breaker with provisions for through the base electrical connections.The circuit breaker will be installed in a water tight enclosure in the unit with access through a swinging door. Wiring will be provided from the switch to the unit high voltage terminal block.The circuit breaker will provide overcurrent protection, be sized per NEC and UL guidelines, and be agency recognized by UL/CSA.
Through the Base Electrical with Disconnect Switch
This
Two inch pleated media filters shall be available on all models.
Factory or Field Installed Options
Clogged Filter/Fan Failure Switch
A dedicated differential pressure switch is available to achieve active fan failure indication and/or clogged filter indication. These indications will be registered with either a zone sensor with status indication lights or an Integrated Comfort™ System. This option is available for microprocessor controlled units.
Differential Pressure Switches
These sensors allow individual fan failure and dirty filter indication for microprocessor controlled units.The fan failure switch will disable all unit functions and “flash” the Service LED on the zone sensor.The dirty filter switch will light the Service LED on the zone sensor and will allow continued unit operation.
Discharge Air Sensing
This option provides true discharge air sensing in heating models.This sensor is a status indicator readable through Tracer™ orTracker™. This option is available for microprocessor controlled units.
Economizer
This accessory shall be available with or without barometric relief.The assembly includes fully modulating
Electric Heaters
Electric heat modules shall be available for installation within basic unit. Electric heater elements shall be constructed of
54 |