Trane PKGP-PRC003-EN manual Data4Ton, Performance, Table PD-10- Continued, Table PD-11- Continued

Models: PKGP-PRC003-EN

1 56
Download 56 pages 28.86 Kb
Page 22
Image 22
Data(4Ton)

Performance

Data(4Ton)

Table PD-10— Belt Drive Evaporator Fan Performance — 4 Ton — WSC048A3,A4,AW — Downflow Airflow

 

 

 

 

 

 

 

 

External Static Pressure (Inches of Water)

 

 

 

 

 

 

 

 

 

 

.10

 

.20

 

.30

 

.40

 

.50

 

.60

.70

 

.80

 

.90

 

1.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

 

 

1-HP Standard Motor & Field Supplied

 

 

 

 

1-HP Standard Motor & Drive

 

 

 

 

 

 

 

Low Static Drive (1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1280

616

0.22

677

0.26

734

0.31

787

0.37

834

0.42

878

0.48

919

0.53

959

0.59

997

0.64

1440

596

0.23

663

0.29

719

0.33

772

0.38

823

0.44

871

0.51

914

0.57

954

0.63

993

0.69

1029

0.75

1600

647

0.31

711

0.37

764

0.42

813

0.47

860

0.53

906

0.59

951

0.66

992

0.74

1029

0.80

1065

0.87

1760

701

0.41

758

0.46

811

0.52

856

0.58

901

0.64

944

0.70

986

0.77

1027

0.85

1066

0.93

1102

1.00

1920

755

0.52

807

0.57

859

0.64

903

0.71

945

0.77

985

0.83

1024

0.89

1063

0.97

1101

1.05

1137

1.14

Table PD-10 — Continued

 

 

 

External Static Pressure (Inches of Water)

 

 

 

1.10

1.20

1.30

1.40

1.50

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

 

1-HP Standard Motor & Drive

 

 

 

 

 

1280

1033

0.70

1069

0.77

1103

0.83

1136

0.89

1170

0.96

1440

1066

0.81

1099

0.87

1133

0.94

1165

1.01

1196

1.08

1600

1099

0.93

1132

1.00

1166

1.07

1196

1.14

1228

1.21

1760

1136

1.08

1168

1.15

1200

1.22

1229

1.29

1920

1172

1.23

1205

1.31

1236

1.39

For Standard Evaporator Fan Speed (RPM), reference Table PD-20. Notes:

Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.

Refer to Table PD-23 to determine additional static pressure drop due to other options/accessories.

Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.

1.Field Supplied Fan Sheave AK61 required. Field Supplied Belt may be necessary.

Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.

Table PD-11 — Belt Drive Evaporator Fan Performance — 4 Ton — WSC048A3,A4,AW — Horizontal Airflow

 

 

 

 

 

 

 

 

External Static Pressure (Inches of Water)

 

 

 

 

 

 

 

 

 

.10

 

.20

 

.30

 

.40

 

.50

 

.60

 

.70

 

.80

.90

 

1.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

 

 

1-HP Standard Motor & Field Supplied

 

 

 

 

1-HP Standard Motor & Drive

 

 

 

 

 

 

 

 

Low Static Drive (1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1280

604

0.20

683

0.26

756

0.32

816

0.39

869

0.45

920

0.51

967

0.57

1011

0.64

1052

0.71

1090

0.79

1440

660

0.28

731

0.34

800

0.41

862

0.48

914

0.54

963

0.61

1009

0.68

1053

0.76

1094

0.83

1133

0.91

1600

717

0.36

783

0.43

846

0.51

907

0.58

961

0.66

1008

0.73

1053

0.81

1095

0.89

1135

0.97

1174

1.05

1760

774

0.47

837

0.54

894

0.62

952

0.70

1006

0.79

1054

0.87

1098

0.95

1139

1.04

1178

1.12

1216

1.21

1920

833

0.59

892

0.67

946

0.76

998

0.85

1050

0.94

1100

1.03

1144

1.12

1185

1.21

1224

1.30

1259

1.39

Table PD-11 — Continued

 

 

 

External Static Pressure (Inches of Water)

 

 

 

1.10

1.20

1.30

 

1.40

 

1.50

 

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

 

1-HP Standard Motor & Drive

 

 

 

 

 

1280

1125

0.86

1160

0.94

1192

1.01

1223

1.08

1254

1.15

1440

1169

0.98

1204

1.07

1237

1.15

1269

1.23

1300

1.32

1600

1211

1.13

1247

1.21

1280

1.30

1312

1.39

1343

1.48

1760

1253

1.30

1289

1.39

1322

1.47

1920

1295

1.48

1-HP Standard Motor &Field Supplied High Static Drive (2)

1-HP Standard Motor &Field Supplied High Static Drive (2)

For Standard Evaporator Fan Speed (RPM), reference Table PD-20. Notes:

Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.

Refer to Table PD-23 to determine additional static pressure drop due to other options/accessories

Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.

1.Field Supplied Fan Sheave AK61 required. Field Supplied Belt may be necessary.

2.Field Supplied Fan Sheave AK41 required. Field Supplied Belt may be necessary.

Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.

22

PKGP-PRC003-EN

Page 22
Image 22
Trane PKGP-PRC003-EN manual Data4Ton, Performance, Table PD-10- Continued, Table PD-11- Continued

FAQ

What is the performance data for the Trane PKGP-PRC003-EN 4 Ton heat pump?

The performance data includes evaporator fan performance and external static pressure inches of water for downflow and horizontal airflow.

Are additional accessories or options included in the pressure drop data?

No, the data includes pressure drop due to standard filters and wet coils. Refer to Table PD-23 to determine additional static pressure drop due to other options/accessories.

What type of motors are used in Trane heat pumps?

Factory supplied motors in commercial equipment are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions.