Performance
Data(3Ton)
Table | Heating Capacities (Net) WSC036A1 At 1200 CFM |
|
|
|
|
|
| |||||||
Outdoor | InstantaneousHeatingCapacity(Btuh/1000) |
| IntegratedHeatingCapacity(Btuh/1000) | Total Power in Kilowatts at | ||||||||||
Temp |
| at Indicated Indoor Dry Bulb Temp. |
|
|
| at Indicated Indoor Dry Bulb Temp.1 |
|
| Indicated Indoor Dry Bulb Temp. | |||||
F. | 60 | 70 | 75 | 80 |
| 60 | 70 | 75 | 80 | 60 | 70 | 75 | 80 | |
9.9 | 8.8 | 8.1 | 7.5 |
| 8.9 | 7.9 | 7.3 | 6.8 | 2.32 | 2.36 | 2.38 | 2.39 | ||
12.0 | 10.8 | 10.2 | 9.5 | 10.8 | 9.7 | 9.2 | 8.6 | 2.42 | 2.47 | 2.49 | 2.51 | |||
2 | 14.2 | 12.9 | 12.3 | 11.6 | 12.8 | 11.6 | 11.1 | 10.4 | 2.51 | 2.57 | 2.60 | 2.62 | ||
7 | 16.5 | 15.2 | 14.5 | 13.8 | 14.9 | 13.7 | 13.1 | 12.4 | 2.60 | 2.67 | 2.71 | 2.73 | ||
12 | 18.8 | 17.5 | 16.8 | 16.1 | 16.9 | 15.8 | 15.1 | 14.5 | 2.69 | 2.77 | 2.81 | 2.84 | ||
17 | 21.1 | 19.9 | 19.2 | 18.5 | 19.0 | 17.9 | 17.3 | 16.7 | 2.77 | 2.87 | 2.91 | 2.95 | ||
22 | 23.5 | 22.2 | 21.5 | 20.9 | 21.2 | 20.0 | 19.4 | 18.8 | 2.85 | 2.96 | 3.01 | 3.06 | ||
27 | 26.1 | 24.6 | 23.9 | 23.1 | 23.5 | 22.1 | 21.5 | 20.8 | 2.94 | 3.05 | 3.11 | 3.16 | ||
32 | 28.7 | 27.2 | 26.4 | 25.6 | 25.8 | 24.5 | 23.8 | 23.0 | 3.02 | 3.15 | 3.21 | 3.27 | ||
37 | 31.3 | 29.7 | 28.9 | 28.1 | 28.2 | 26.7 | 26.0 | 25.3 | 3.11 | 3.25 | 3.32 | 3.38 | ||
42 | 33.9 | 32.2 | 31.4 | 30.6 | 30.5 | 29.0 | 28.3 | 27.5 | 3.20 | 3.35 | 3.42 | 3.50 | ||
47 | 36.6 | 34.8 | 33.9 | 33.1 | 36.6 | 34.8 | 33.9 | 33.1 | 3.29 | 3.45 | 3.53 | 3.61 | ||
52 | 39.2 | 37.4 | 36.5 | 35.6 | 39.2 | 37.4 | 36.5 | 35.6 | 3.39 | 3.57 | 3.65 | 3.74 | ||
57 | 41.9 | 38.7 | 37.8 | 36.8 | 41.9 | 38.7 | 37.8 | 36.8 | 3.49 | 3.66 | 3.75 | 3.85 | ||
62 | 43.2 | 41.3 | 40.4 | 39.4 | 43.2 | 41.3 | 40.4 | 39.4 | 3.57 | 3.78 | 3.89 | 3.99 | ||
67 | 45.9 | 43.9 | 42.9 | 41.9 | 45.9 | 43.9 | 42.9 | 41.9 | 3.69 | 3.92 | 4.02 | 4.13 | ||
72 | 48.6 | 46.5 | 45.5 | 44.4 | 48.6 | 46.5 | 45.5 | 44.4 | 3.81 | 4.05 | 4.17 | 4.28 |
For other airflow conditions, see heating capacity correction factor (Table
Net heating capacity and power input includes indoor fan heat at ARI esp. To obtain net heating at other conditions, subtract fan heat at this condition and add fan heat at new condition. Note:
1. Integrated heating capacities and powers include the effects of defrost in the frost region. All heating capacities and power (kw) are at 70% OD relative humidity and demand defrost cycle.
Table | Heating Capacities (Net) |
| WSC036A3, A4, AW | At 1200 CFM |
|
|
|
|
| ||||||||
Outdoor |
| InstantaneousHeatingCapacity(Btuh/1000) |
|
| IntegratedHeatingCapacity(Btuh/1000) | Total Power in Kilowatts at | |||||||||||
Temp. |
|
| at Indicated Indoor Dry Bulb Temp. |
|
|
|
| at Indicated Indoor Dry Bulb Temp.1 |
|
| Indicated Indoor Dry Bulb Temp. |
| |||||
F. | 60 | 70 | 75 | 80 |
| 60 | 70 | 75 | 80 |
| 60 | 70 | 75 | 80 |
| ||
9.6 | 8.6 | 8.1 | 7.5 |
| 8.6 | 7.7 | 7.3 | 6.8 |
| 2.14 | 2.21 | 2.23 | 2.25 |
| |||
11.7 | 10.7 | 10.1 | 9.5 |
| 10.5 | 9.6 | 9.1 | 8.6 |
| 2.25 | 2.32 | 2.35 | 2.38 |
| |||
2 | 13.9 | 12.8 | 12.3 | 11.6 |
| 12.5 | 11.5 | 11.1 | 10.4 |
| 2.36 | 2.44 | 2.47 | 2.50 |
| ||
7 | 16.3 | 15.1 | 14.5 | 13.9 |
| 14.7 | 13.6 | 13.1 | 12.5 |
| 2.46 | 2.54 | 2.58 | 2.62 |
| ||
12 | 18.6 | 17.4 | 16.8 | 16.1 |
| 16.7 | 15.7 | 15.1 | 14.5 |
| 2.55 | 2.65 | 2.69 | 2.73 |
| ||
17 | 20.9 | 19.8 | 19.2 | 18.5 |
| 18.8 | 17.8 | 17.3 | 16.7 |
| 2.64 | 2.75 | 2.80 | 2.85 |
| ||
22 | 23.4 | 22.1 | 21.5 | 20.8 |
| 21.1 | 19.9 | 19.4 | 18.7 |
| 2.73 | 2.85 | 2.90 | 2.95 |
| ||
27 | 26.0 | 24.6 | 23.9 | 23.2 |
| 23.4 | 22.1 | 21.5 | 20.9 |
| 2.82 | 2.95 | 3.00 | 3.06 |
| ||
32 | 28.6 | 27.2 | 26.4 | 25.7 |
| 25.7 | 24.5 | 23.8 | 23.1 |
| 2.91 | 3.04 | 3.11 | 3.17 |
| ||
37 | 31.2 | 29.7 | 28.9 | 28.2 |
| 28.1 | 26.7 | 26.0 | 25.4 |
| 3.00 | 3.14 | 3.21 | 3.28 |
| ||
42 | 33.9 | 32.2 | 31.4 | 30.6 |
| 30.5 | 29.0 | 28.3 | 27.5 |
| 3.09 | 3.24 | 3.32 | 3.39 |
| ||
47 | 36.5 | 34.8 | 34.0 | 33.1 |
| 36.5 | 34.8 | 34.0 | 33.1 |
| 3.18 | 3.34 | 3.42 | 3.50 |
| ||
52 | 39.2 | 37.4 | 36.5 | 35.6 |
| 39.2 | 37.4 | 36.5 | 35.6 |
| 3.28 | 3.45 | 3.53 | 3.62 |
| ||
57 | 41.8 | 38.7 | 37.8 | 36.8 |
| 41.8 | 38.7 | 37.8 | 36.8 |
| 3.37 | 3.53 | 3.63 | 3.72 |
| ||
62 | 43.2 | 41.3 | 40.3 | 39.3 |
| 43.2 | 41.3 | 40.3 | 39.3 |
| 3.44 | 3.65 | 3.75 | 3.85 |
| ||
67 | 45.8 | 43.9 | 42.9 | 41.8 |
| 45.8 | 43.9 | 42.9 | 41.8 |
| 3.55 | 3.76 | 3.87 | 3.98 |
| ||
72 | 48.5 | 46.4 | 45.4 | 44.3 |
| 48.5 | 46.4 | 45.4 | 44.3 |
| 3.65 | 3.88 | 4.00 | 4.11 |
|
For other airflow conditions, see heating capacity correction factor (Table
Net heating capacity and power input includes indoor fan heat at ARI esp. To obtain net heating at other conditions, subtract fan heat at this condition and add fan heat at new condition. Note:
1. Integrated heating capacities and powers include the effects of defrost in the frost region. All heating capacities and power (kw) are at 70% OD relative humidity and demand defrost cycle.
29 |